Instruction Manual

PSM SERIES PROGRAMMABLE POWER SUPPLY
PROGRAMMER MANUAL
33
:VOLTage:STEP
Function:
Set or query the voltage step size.
Syntax:
:VOLTage:STEP {<Decimal number>|DEFault}
:VOLTage:STEP? [DEFault]
Examples:
1) :VOLTage:STEP 1.0 sets the step size to 1.0V for voltage
programming with the VOLTage:UP and VOLTage:DOWN
command .The immediate voltage level increases or decreases by the
value of the step size.
2) :VOLTage:STEP DEF sets the step size to minimum resolution
0.5mV(PSM-2010).
3) :VOLTage:STEP? returns the present voltage step size.
4) :VOLTage:STEP? DEF returns the minimum resolution step size
0.5mV(PSM-2010).
:CURRent:TRIGgered
Function:
Set or query the triggered current level.
Syntax:
:CURRent:TRIGgered {<Decimal number>|MIN|MAX}
:CURRent:TRIGgered? [MIN|MAX]
Examples:
1) :CURRent:TRIGgered 1.0 sets the triggered current to
1.0000A(PSM-2010).
PSM SERIES PROGRAMMABLE POWER SUPPLY
PROGRAMMER MANUAL
34
2) :CURRent:TRIGgered MAX sets the triggered current to the highest
programmable triggered current levels.
3) :CURRent:TRIGgered MIN sets the triggered current to
0.0000A(PSM-2010).
4) :CURRent:TRIGgered? returns the present triggered current level.
5) :CURRent:TRIGgered? MAX returns the highest programmable
triggered current level.
6) :CURRent:TRIGgered? MIN returns the lowest programmable
triggered current level.
:VOLTage:TRIGgered
Function:
Set or query the triggered voltage level.
Syntax:
:VOLTage:TRIGgered {<Decimal number>|MIN|MAX}
:VOLTage:TRIGgered? [MIN|MAX]
Examples:
1) :VOLTage:TRIGgered 1.0 sets the triggered voltage to
1.0000V(PSM-2010).
2) :VOLTage:TRIGgered MAX sets the triggered voltage to the highest
programmable triggered voltage levels.
3) :VOLTage:TRIGgered MIN sets the triggered voltage to
0.0000V(PSM-2010).
4) :VOLTage:TRIGgered? returns the present triggered voltage level.
5) :VOLTage:TRIGgered? MAX returns the highest programmable
triggered voltage level.