RESIDENTIAL SERIES BLACK POLYESTER CORE
• Rated pressure per UL 181: 12" W.C. positive,
3
/
4
" W.C. negative (1/2" W.C. neg for 14" – 20" diameter)
• Recommended operating pressure:
6" W.C. positive for 12" diameter and under
4" W.C. positive for 14" diameter and over
• Rated maximum air velocity: 5000 FPM
• For residential and light commercial applications
COMMERCIAL SERIES
METALIZED POLYESTER CORE
• Rated pressure per UL 181: 16" W.C. positive,
1" W.C. negative (1/2" W.C. neg for 14" – 20" diameter)
• Recommended operating pressure:
6" W.C. positive for 12" diameter and under
4" W.C. positive for 14" diameter and over
• Rated maximum air velocity: 6000 FPM
• For residential and most commercial applications
COMMERCIAL SERIES
CORRUGATED ALUMINUM CORE
• Maximum rated pressure per UL 181:
12" W.C. positive for 10" diameter and under
8" W.C. positive for 12" diameter and over
3" W.C. maximum negative
• Rated maximum air velocity: 5000 FPM
INSULATION R-VALUES
• Certified by Underwriters Laboratories Inc. and
the Air Diffusion Council in accordance with ADC
Flexible Duct Performance and Installation Standards
using ASTM C-518 at installed wall thickness on flat
insulation only
POLYETHYLENE JACKETS
• A durable black polyethylene vapor barrier
• High tensile scrim is used under the vapor barrier to
provide additional strength and tear resistance
• Perm rating of 0.1 (ASTM E96 Method "A")
METALIZED JACKETS
• A metalized polyester vapor barrier is constructed
by sandwiching fiberglass scrim between layers of
polyester to provide an outstanding combination of
strength and tear resistance
• Perm rating of 0.04 (ASTM E96 Method "A")
SURFACE BURNING CHARACTERISTICS
(Class 1 Air Ducts)
• Maximum flame spread: 25
• Maximum smoke developed: 50
OPERATING TEMPERATURE RANGE
• -20°F to 140°F continuous @ max. Pos. pressure
• -20°F to 180°F intermittent @ 2" W.C. Pos. pressure
• -20°F to 250°F intermittent @ 0.5" W.C. Pos. pressure
• For corrugated aluminum cores:
-100°F to 250°F continuous @ max Pos. pressure
CODE APPROVALS, CERTIFICATIONS,
AND LISTINGS
• UL 181 Listed • NFPA 90A and 90B
• IMC • HUD
• UMC
• California Bureau of Home Furnishings
• Most Federal, State, and Local codes and standards
Performance Data
3
Product Information
OUTSTANDING PERFORMANCE. All Hart & Cooley
flexible duct products are performance-tested in accordance
with industry standards to ensure reliability and years of
service. Our core is tested (in accordance with ADC FD 72-R1)
for actual installation static pressure/ temperature performance
and meets the ratings specified in our catalog. Our polyester
cores are also tested for microbial resistance by GEI per
ASTM D6329-98. The vapor barriers are tested for permeation
in accordance with ASTM test methods. Call-backs are
expensive and eat away at your profits. Use flexible duct you
know has been performance-tested.
INDUSTRY INVOLVEMENT.
Hart & Cooley is committed to the flexible
duct industry and supports it through
involvement in many industry-related
associations, committees, and organizations.
Participation in Air Diffusion Council and
Underwriters Laboratories, Inc. industry
advisory council allows Hart & Cooley to stay at the forefront of
industry changes.
MEMBER