Operation Manual

1 6E 6127.c
6E 6127.c
7
6
on
off
5
4
3
2
1
ON
OFF
enter
reset
prog
auto
manu
EG170
§
1 channel time switch -
weekly cycle
User instruction
Æ
Working principle :
The EG170 is a time switch for the automatic
control of electrical loads.
It is fully programmable with a maximum of 20
program steps. Each program step can be
applied to one or several days, maximising the
use of each memory location.
The front cover is sealable preventing
unauthorised access after completion of
programming.
Warning : at the beginning of use, please
reset the device in order to clear the memory
before programming.
This is achieved by using a pen to push the
reset button.
Presentation :
Display :
time
circuit status (ON or OFF)
day of the week
(1 = Monday, 2 = Tuesday ....)
Buttons :
Mode selector : to select one of the
following modes :
time setting
prog programming
auto running mode
manu manual override
1” to “7” : selection of the days
on/off” : chooses whether the circuit
is on or off
+” and “-” : changes settings
enter” : to confirm
reset
Time and day setting :
1. Move mode selector to
2. Select with key “1” to “7” , the actual day
(1=Monday, 2 = Tuesday .)
3. Input time with buttons “+” and “-”.
Important :
The clock starts when exiting the time setting mode.
Programming :
1. Move mode selector to “prog”.
2. Select with keys “1” to “7” the day(s) assigned
to this program step. An arrow appears
above each day concerned.
3. Input switching time with buttons “+” and “-”.
4. Input the type of switching with button “on/off
(for the first action ON is automatically proposed).
5. Enter this program step with button “enter”.
Program additional time settings by repeating
steps 2 to 5.
Important :
To activate the program, move mode selector to
auto”.
Running Auto mode
This mode is the current displaying mode.
It does not allow any modification.
Move mode selector to “auto”.
Display of the time, the day and the state of
the channel.
To check your program :
1. Move mode selector to “prog”.
2. Press the “enter” key repeatedly to display
the different program steps (switching time,
days of the week and state of the channel
ON or OFF).
To override the output :
Permanent override :
1. Move mode selector to “manu”.
2. Select the state of the output with key
on/off”.
To switch back to automatic mode, move
mode selector to “auto”.
1234 56 7
4
5
1
6 7 8 9
3
2
enter
reset
on
off
prog
auto
manu
OFF
1234 56 7
enter
reset
on
off
prog
auto
manu
To modify or delete a program step :
1. Move mode selector to “prog”.
2. Press “enter repeatedly and select the
program step to modify or to delete.
3. Modify :
- switching time with keys “+ or “-
- days assigned with keys “1” to “7”.
(an arrow flashes above all days assigned,
press once to add a day, press twice to
cancel).
- state of the channel with key “on/off”.
To delete a program step, press keys “1” to “7
in order to cancel all days assigned.
4. Confirm with the “enter” key.
EG170
345621
L
N
Technical specifications :
Electrical characteristics :
- supply voltage : 230V AC +10/-15% 50/60Hz
- output : 1 changeover contact
μ 16A - 250V AC1.
μ 3A - 250V cos ϕ = 0,6
1000 W incandescent lighting
- power consumption : 1 VA
- protection degree : IP20
- insulation class : II
Functional characteristics :
- accuracy : ± 1sec. / day at 20 °C
- operating reserve : lithium battery, total of
three years.
Environment :
Operating temperature : -10 to +50 °C
Storage temperature : -10 to +50 °C
Connection tunnel terminals :
flexible : 0,5 to 2.5 mm
2
rigid : 0,5 to 4 mm
2
Dimensions : 3 modules (3x17,5mm)
Electrical connections :
1. Move mode selector to “manu”.
2. Select the state of the output with key
on/off”.
3. Input with key “+” and “-” the override duration :
from 1 to 23 hours by steps of 1 hour.
Then from 1 to 27 days by steps of 1 day.
4. Move mode selector to “auto”.
The state indication is flashing. This means a
timed override. Return to the initial program
after the duration.
To reset the time switch :
Press “reset“ to clear the program.
1. Move mode selector to “manu”.
2. Press key “-” or “+until display -h.
3. Move mode selector to “auto” to switch
back to automatic mode.
Timed override :
To cancel the timed override :
A warranty period of 24 months is offered on hager products,
from date of manufacture, relating to any material of manufac-
turing defect. If any product is found to be defective it must be
returned via the installer and supplier (wholesaler). The warranty
is withdrawn if :
- after inspection by hager quality control dept the device is
found to have been installed in a manner which is contrary to
IEE wiring regulations and accepted practice within the industry at
the time of installation.
- the procedure for the return of goods has not been followed.
Explanation of defect must be included when returning goods.
Warranty
GB
1234 56 7
enter
reset
on
off
prog
auto
manu
ON
1234 56 7
enter
reset
on
off
prog
auto
manu
ON
1234 56 7
enter
reset
on
off
prog
auto
manu
ON
1234 56 7
enter
reset
on
off
prog
auto
manu
ON
1
2
34 56 7
enter
reset
on
off
prog
auto
manu