Installation Guide
Protection Devices
Surge Protection Kit
1
ZD0906
ZD0906
ZD0906
1
2
3
1. Busbar
2. 6mm sq earth cable
3. Type II Surge Protection
VME02SPD
Installation
Instructions
Move the main switch over 2 modules and clip the Surge
protection device on the right hand side of the main switch.
Loosen the L&N screws on the main switch and
terminate the spade terminals in the Bi connect.
Fit the 6mm earth cable into one of the terminals in the top of
the SPD and terminate in the earth bar. Torque to 3.6Nm.
Push the busbar firmly against the Surge protection device
making sure the cables below are secure secure and torque back
to 3.6Nm.
Surge Protection Kit
5HSODFH
5HG
Fault indication
A
B
A
A
B
Replacement cartridges - SPB015, SPB015N
Loosen the bottom terminals on the Main switch and Surge
protection device and insert the busbar into the rectangle
slots above the cage terminals.