Service Manual

TROUBLESHOOTING & REFERENCES
J-4
ENGLISH
Special Functions
Series IDU
IDU PCB part number Controls Needed
Guide
Reference
Haier GEA Controller IR Reciever Wired Controller
3X3 Cassette AL24LP2VHA 0151800208 WJ26X23559 YR-HBS01 \ Unplug Chart 1
3X3 Cassette AL36LP2VHA 0151800208 WJ26X23559 YR-HBS01 \ Unplug Chart 1
3X3 Cassette AL48LP2VHA 0151800208 WJ26X23559 YR-HBS01 \ Unplug Chart 1
2X2 Cassette AB09SC2VH* 0151800208A WJ26X23785 YR-HBS01 \ Unplug Chart 3
2X2 Cassette AB12SC2VH* 0151800208A WJ26X23785 YR-HBS01 \ Unplug Chart 3
2X2 Cassette AB18SC2VH* 0151800208A WJ26X23785 YR-HBS01 \ Unplug Chart 3
Pro Duct AM24LP2VHA 0151800267 WJ26X23580 YR-HBS01 RE-02(CN21) Unplug Chart 2
Pro Duct AM36LP2VHA 0151800106E WJ26X23585 YR-HBS01 RE-02(CN29) Unplug Chart 2
Pro Duct AM48LP2VHA 0151800106E WJ26X23586 YR-HBS01 RE-02(CN29) Unplug Chart 2
Mid-Static Duct USYM09UCDSA 0151800580 WJ26X27175 YR-HG RE-02(CN29) Unplug Chart 4
Mid-Static Duct USYM12UCDSA 0151800580 WJ26X27175 YR-HG RE-02(CN29) Unplug Chart 4
Mid-Static Duct USYM18UCDSA 0151800580 WJ26X27175 YR-HG RE-02(CN29) Unplug Chart 4
Mid-Static Duct USYM24UCDSA 0151800580 WJ26X27175 YR-HG RE-02(CN29) Unplug Chart 4
Slim Duct AD07SL2VH* 0151800175A WJ26X23178 YR-HBS01 RE-02(CN29) Unplug Chart 2
Slim Duct AD09SL2VH* 0151800175A WJ26X23178 YR-HBS01 RE-02(CN29) Unplug Chart 2
Slim Duct AD12SL2VH* 0151800175A WJ26X23178 YR-HBS01 RE-02(CN29) Unplug Chart 2
Slim Duct AD18SL2VH* 0151800175A WJ26X23178 YR-HBS01 RE-02(CN29) Unplug Chart 2
Highwall AW07EH2VHA A0011001066 WJ26X25213 YR-HG \ \ Chart 4
Highwall AW09EH2VHA A0011001066 WJ26X25213 YR-HG \ \ Chart 4
Highwall AW12EH2VHA A0011001066 WJ26X25213 YR-HG \ \ Chart 4
Highwall AW18EH2VHA A0011007590 WJ26X25413 YR-HG \ \ Chart 4
Highwall AW07LC2VHB A0011800281CA WJ26X23928 YR-HG \ \ Chart 4
Highwall AW09LC2VHB A0011800281CA WJ26X23928 YR-HG \ \ Chart 4
Highwall AW12LC2VHB A0011800281CA WJ26X23928 YR-HG \ \ Chart 4
Highwall AW18LC2VHB A0011800281FA WJ26X23929 YR-HG \ \ Chart 4
Console USYF09UCDWA 0151800579 WJ26X27223 YR-HG \ \ Chart 4
Console USYF12UCDWA 0151800579 WJ26X27223 YR-HG \ \ Chart 4
Console USYF18UCDWA 0151800579 WJ26X27223 YR-HG \ \ Chart 4
Temperature Compensation
This function allows you the capability to adjust the temperature compensation oset of any indoor unit. The adjusted value is
programmed into the EEPROM.
Guide 1
1. Install the grille assembly and connect the power cable.
2. Unplug the wired controller.
3. Connect power to the unit.
4. Press the ON/OFF button on the remote control (HBS-01).
5. (Ignore this step if the display temperature is already
O
C,) Press MENU/OF button to switch the display temperature to
O
C,
then press conrm.
6. Open the front cover of the remote controller, and press the LIGHT button 12 times in 7 seconds.
7. The panel will beep 4 times and display an “A”.
8. Press the LIGHT button once to conrm. The display will read “A0”.
9. Press the button TEMP. or TEMP. until the display shows “A5”.
10. Press the LIGHT button once to conrm. The display will read “0b”.
11. Press the button TEMP. or TEMP. to scroll through the listed
Codes. Each code is associated with a corresponding compensation
value (see table below). For example, if you want make the
temperature invalid, scroll it to 0F.
12. Press the LIGHT button once to conrm. The display will read “A5”.
13. Press the ON/OFF button on the remote control to save the changes.