Submittals

Arctic Multi Series Submittal
Rev. May 2020
Cooling Capacity Data - Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
70
O
F (21
O
C) 75
O
F (24
O
C) 80
O
F (27
O
C)
Total Capacity
(Btu/h)
Power Usage
(w)
Total Capacity
(Btu/h)
Power Usage
(w)
Total Capacity
(Btu/h)
Power Usage
(w)
14
O
F (-10
O
C) 12,320 1,150 13,120 1,180 14,680 1,220
65
O
F (18
O
C) 24,300 1,610 25,010 1,650 26,560 1,720
75
O
F (24
O
C) 23,130 1,710 24,140 1,760 25,310 1,830
85
O
F (29
O
C) 23,310 1,880 24,110 1,920 24,900 1,960
95
O
F (35
O
C) 22,360 1,990 23,060 2,050 24,130 2,070
105
O
F (41
O
C) 21,230 2,220 22,170 2,280 22,690 2,310
115
O
F (46
O
C) 16,830 2,230 17,850 2,320 18,560 2,400
24000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM
3U24EH2VHA
Heating Capacity Data - Non Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
60
O
F (16
O
C) 70
O
F (21
O
C) 77
O
F (25
O
C)
Maximum Heating
Capacity (Btu/h)
Power Usage
(w)
Max Heating
Capacity (Btu/h)
Power Usage
(w)
Max Heating
Capacity (Btu/h)
Power Usage
(w)
-15
O
F (-26
O
C) 18,120 2,960 18,000 3,090 16,580 3,220
-4
O
F (-20
O
C) 19,930 3,060 19,430 3,250 17,330 3,360
5
O
F (-15
O
C) 24,860 3,290 24,120 3,510 21,870 3,620
17
O
F (-8
O
C) 28,210 3,390 27,220 3,810 25,500 3,920
47
O
F (8
O
C) 31,230 3,720 29,600 4,030 27,850 4,120
Heating Capacity Data - Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
60
O
F (16
O
C) 70
O
F (21
O
C) 77
O
F (25
O
C)
Maximum Heating
Capacity (Btu/h)
Power Usage
(w)
Max Heating
Capacity (Btu/h)
Power Usage
(w)
Max Heating
Capacity (Btu/h)
Power Usage
(w)
-15
O
F (-26
O
C) 18,000 3,480 17,100 3,360 16,100 3,530
-4
O
F (-20
O
C) 19,820 3,510 19,200 3,560 17,200 3,610
5
O
F (-15
O
C) 22,860 3,440 23,240 3,540 21,160 3,730
17
O
F (-8
O
C) 27,140 3,470 26,410 3,620 24,170 3,810
47
O
F (8
O
C) 29,130 3,550 28,820 3,780 27,660 3,920
Cooling Capacity Data - Non Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
70
O
F (21
O
C) 75
O
F (24
O
C) 80
O
F (27
O
C)
Total Capacity
(Btu/h)
Power Usage
(w)
Total Capacity
(Btu/h)
Power Usage
(w)
Total Capacity
(Btu/h)
Power Usage
(w)
14
O
F (-10
O
C) 13,210 1,080 14,010 1,120 15,330 1,190
65
O
F (18
O
C) 24,860 1,560 25,940 1,610 27,480 1,690
75
O
F (24
O
C) 23,560 1,680 24,860 1,710 26,190 1,780
85
O
F (29
O
C) 23,350 1,710 24,560 1,790 25,430 1,840
95
O
F (35
O
C) 22,860 1,860 23,360 1,880 24,320 1,910
105
O
F (41
O
C) 21,320 2,060 22,720 2,160 23,560 2,190
115
O
F (46
O
C) 16,960 2,120 18,160 2,190 18,680 2,230
Capacity output and power usage are measured approximately at 50% indoor RH.
Capacities are obtained at standard piping length of each outdoor model
Specications are subject to change without notice. © 2019 GE Appliances, a Haier Company All rights reserved