Spec Sheet

6 31-5000411 Rev. 0
ENGLISH
SYSTEM
Part 1: General
1.1 Description
A. The Haier Advanced Plus heat pump air conditioner shall be a variable capacity, mini-split type system
comprised of a single outdoor and a single wall-mounted indoor unit.
1.2 Toxicity
A. The heat pump system shall participate in RoHS compliance and listed in the directory.
Part 2: Performance and Operating Range
2.1 Operating Range
A. The heat pump shall provide cooling temperature range of 14°~115°F (-10°C~46°C)
B. The heat pump system shall be capable of providing greater than 70% capacity at -15°F (-26°C) outdoor
ambient temperature.
C. The heat pump system shall be capable of 100% rated heating capacity at 5°F (-15°C) outdoor ambient
temperature.
D. The heat pump shall operate normally with voltages between 187~253V.
2.2 Performance
The system shall perform within the specified operating window found on the following table.
A. Cooling performance rating shall be verified following AHRI 210/240 standards of 80°F DB/67°F WB (27°/19°C)
indoor temperature and 95°F DB/75°F WB (35°/24°C) outdoor temperature.
B. Heating performance rating shall be verified following AHRI 210/240 standards of 70°F DB/60°F WB (21°/16°C)
indoor temperature and 47°F DB/43°F WB (8°/6°C) outdoor temperature.