Advanced Plus Series Submittal
Rev. May 2019
Electrical Requirement
Power Supply
208/230V, 1 Phase,
60 HZ
Operating Voltage Range 187~253 VAC
Recommended Fuse/Breaker Size 15A
MCA 11A
Operating Range
Cooling 14~115°F (-10~46°C)
Heating -15~75°F (-26~24°C)
CUS
Intertek
12000 BTU/HR WALL MOUNTED INVERTER DRIVEN HEAT PUMP SYSTEM
1U12AP2VHA / AW12ES2VHB
Pipe Length
Minimum Pipe Length 6 ft
Maximum Pipe Length 50 ft
Maximum Pipe Height Dierence 33 ft
Connection
1/4”(Discharge)
3/8”(Suction) Flare
For more information visit us:
www.Haierductless.com
www.Haierductlesshelp.com
Heating Performance
Rated Heating Capacity 13,000 BTU
Heating Capacity Range 3,900~20,000 BTU
Rated Power Input 1,500 W
HSPF 11.0
Cooling Performance
Rated Cooling Capacity 12,000 BTU
Cooling Capacity Range 3,300~15,000 BTU
Rated Power input 960 W
SEER 23.0
EER 12.5
Moisture Removal 3.9 Pt./Hr
Accessories
Connecting cable to indoor units must be 14/4 AWG unshielded stranded
copper. Cable must be ran continuous, without splicing.
Remote Controller
Ships with YR-HG
Wired Controller
Compatible with wired controllers YR-E17, YR-E16B,
and QACT17A. All wired controllers require interface kit
WK-B.
WiFi
Compatible with WiFi adapter QAWF01A.
Wind Bae
Uses wind bae QAWB42A
Job Name: __________________________________
Purchaser: __________________________________
Submitted To: _______________________________
Construction: _______________________________
Reference: __________________________________
Approval: ___________________________________
Date: ______________________________________
Submitted By: _______________________________
Unit: _______________________________________
Drawing #: __________________________________