Leak Test
3.1
Step - 3.1
Refrigerant piping connections for the mini-split system are


use caution to prevent dirt or debris from entering the tubing.
Remember to place the nut on the pipe before creating the

3.2
Step - 3.2
To join the lineset piping together, directly align the piping


connection.
3.3
Step - 3.3

standard wrench, and one torque wrench. See Table 1 for the

Step 3.1
Half union
Flarenut
Torque wrench
Spanner
Forced fasteningwithout carefulcentering may
damagethe threads and cause a leakageofgas.
Pipe Diameter(ǿ)Fastening torque
Liquid side6.35mm(1/4") 18N.m/13.3Ft.lbs
Liquid/Gas side9.52mm(3/8") 42 N.m/30.1Ft.lbs
Gasside12.7mm(1/2") 55N.m/40.6Ft.lbs
Gasside15.88mm(5/8") 60 N.m/44.3Ft.lbs
Table 1
Step 3.2
Step 3.3
Hazard of Explosion! Never use an open ame to detect
gas leaks. Explosive conditions may occur. Use a leak test
solution or other approved methods for leak testing. Failure
to follow recommended safe leak test procedures could
result In death or serious injury or equipment or property
damage.
Use only dry nitrogen with a pressure regulator for
pressurizing unit. Do not use acetylene, oxygen or
compressed air or mixtures containing them for pressure
testing. Do not use mixtures of a hydrogen containing
refrigerant and air above atmospheric pressure for pressure

an explosion. Refrigerant, when used as a trace gas should
only be mixed with dry nitrogen for pressurizing units. Failure
to follow these recommendations could result in death or
serious injury or equipment or property damage.
Step 4.1
Piping Connection
Step 3 - Refrigerant Line Connections
Step 4 - Leak Test and Evacuation
4.1
Step - 4.1
Using a tank of nitrogen with attached regulator, charge
the system with 150 PSIG of dry nitrogen. Use adapter AD-


methods. If a leak is detected, repair and recheck. If no leaks
are detected, proceed to evacuate the system.