Haier air conditioner Edition: 20070116 Domestic Air conditioner HSU-09HSA03/R2(DB) HSU-12HSA03/R2(DB) CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE. THIS MANUAL IS USED BY QUALIFIED APPLIANCE TECHNICIANS ONLY. HAIER DOES NOT ASSUME ANY RESPONSIBILITY FOR PROPERTY DAMAGE OR PERSONAL INJURY FOR IMPROPER SERVICE PROCEDURES DONE BY ONE UNQUALIFIED PERSON.
Haier air conditioner Edition: 20070116 CONTENTS 1. GENERAL INFORMATION...............................................................3 2. SPECIFICATION...............................................................................6 3. ELECTRICAL CONTROL..................................................................8 4. THERMISTER RESISTANCE CHART.............................................30 5. TROUBLE SHOOTING....................................................................40 6.
Haier air conditioner Edition: 20070116 1. General information This Service Manual describes the operation, disassembly, troubleshooting, and repair of Haier Room Air Conditioners, etc. It is intended for use by authorized services who troubleshoot and repair these units. It is assumed that users of this manual are familiar with the use of tools and equipment used to troubleshoot and repair electrical, mechanical, and refrigeration systems; and understand the terminology used to describe and discuss them.
Haier air conditioner Edition: 20070116 MODEL: HSU-09HSA03/R2(DB) Product Features Main Specification Cooling Capacity: 2400W Power Input: 680W Current Input:3.50A EER:3.53 Heating Capacity: 2650W Power Input:730W Current Input: 3.8A COP: 3.
Haier air conditioner Edition: 20070116 MODEL: HSU-12HSA03/R2(DB) Product Features Main Specification Cooling Capacity: 3300W Power Input: 1078W Current Input: 4.9A EER:3.06 Heating Capacity: 3600W Power Input:1230W Current Input: 5.4A COP: 2.
Haier air conditioner Edition: 20070116 2. Specification Item Unit Power PH, V, Hz Climate Type 1, 230, 50 /R2(DB) 1,230,50 T1 A 10 12 Cooling Capacity W 2400 3300 Rated Power W 680 1078 Rated Current A 3.50 4.9 Max Power W 870 1350 Max Current A 3.8 6.0 W/W 3.53 3.06 Heating Capacity W 2650 3600 Rated Power W 730 1230 Rated Current A 3.8 5.4 Max Power W 1100 1480 Max Current A 4.4 6.8 W/W 3.63 2.
Haier air conditioner Type Edition: 20070116 R410A R410A g 800 1200 g/m 12 Liquid pipe Diameter mm 6.35 6.35 Gas pipe Diameter mm 9.52 12.
Haier air conditioner Edition: 20070116 3. Electrical control ĉ. Scope of Application This specification use for HSU-09/12HSA03/R2˄DB˅frequency conversion air condition are manufactured by Haier air condition parent company. "Setting value" (express in parameter) in this specification means is a parameter that is stored in EEPROM. Refer to [EEPROM parameter table]. 1.
Haier air conditioner Edition: 20070116 32 PA6 pushup stepping motor C 33 34 PA7 PTB0/ATD0 pushup stepping motor D output outdoor communication 35 36 37 PTB1/ATD1 PTB2/ATD2 PTB3/ATD3 input outdoor communication room temperature inner coil 38 39 PTB4/ATD4 PTB5/ATD5 swing left stepping motor D swing left stepping motor C 40 41 PTB6/ATD6 PTB7/ATD7 swing left stepping motor B swing left stepping motor A 42 43 PTD0 PTD1 44 VDDAREF VCC 45 AVSS/VREFL GND 46 PTD2 swing right stepping moto
Haier air conditioner Edition: 20070116 2.1.1 Standard of temperature sensor under indoor environment. When the line is in short circuit or open circuit, the indicator light will be alarming and the indoor fan motor will be off. It will resume to the original state automatically after it returns normally, and operates as usual. Short circuit: Temperature: above 126 degrees, Hex: Above F8H, Value of Resistance: Below 0.65K, above 4.85V.
Haier air conditioner Mode Corrected variable Correct the operating mode ETBL0 4.67ć ETBL1 6ć ETBL2 4.67ć When the air capacity is low to correct it ETBL3 4.67ć Correct the operating mode ETBL4 -0.33ć ETBL5 -4ć When the air capacity is low to correct it Cool and dry mode Corrected Corrected contents Correct forced operating mode Heat Edition: 20070116 Correct the forced operating mode parameter 2.4 Control the temperature the area 2.4.
Haier air conditioner Edition: 20070116 When the system is in test run, emergency operation, silencing operation mode, the DASH will be stopped. 2.4.5 Temperature adjustment section˄DASH operation condition in the different mode˅ 2.4.6 Frequency in the different mode In this area, the frequency (from indoor to outdoor) indication as following: When the system is in the cool and dry mode, the frequencies between A area and B area are same.
Haier air conditioner Edition: 20070116 Controlling table in the identity area˖ Temperature change area A B Heat Cool and dry FQUPH˖2Hz˗ C D E F G FQUP(2Hz) FQUP(2Hz) FQUP(2Hz) FQUP(1Hz) FQUP(1Hz) FQUP(2Hz) FQUP(2Hz) FQUP(2Hz) FQUP(1Hz) FQUP(1Hz) FQUPL˖1Hz 2.4.8 Air capacity decision when Air capacity is running automatically. When air capacity is running automatically, based on temperature adjusting sections, you shift the switch for air capacity, namely, enhanced, middle, and weak.
Haier air conditioner Edition: 20070116 correction the limit frequency according to the following condition: Outdoor temperature condition Indication frequency 011(20ćmore than) Low fan or health fan limited frequency 48Hz 010(15-20ć) Low fan or health fan limited frequency +FUPHEA1 50Hz 001(10-15ć) Low fan or health fan limited frequency 52Hz 000(10ćdownward) +FUPHEA2 In general frequency ċ.
Haier air conditioner Edition: 20070116 Based on the heat exchange temperature to control the indoor fan as the above shown. 1. When the heat exchange temperature rise, to distinguish the fan speed based on the heat exchange temperature: The heat exchange temperature is less than 35.2ć, the speed of fan motor is weak (for the first power on, when the system operating in heat mode or OFF the defrost mode, and when the heat exchange temperature is less than 25.
Haier air conditioner Edition: 20070116 3.1.2 Compressor OFF and waiting for 3 minutes 1. The compressor is OFF (the flamestat is OFF), the air capacity will change from small to little small after 20 seconds (is SSLO in silence mode); 2. To heat operating in stand-by time (when the mode switch, the compressor will OFF), the air capacity keep to weak. 3. Power off by remote controlˈthen the indoor fan motor will OFF. 3.1.
Haier air conditioner Edition: 20070116 3.3.2 Compressor ON When the air capacity is set High, Middle and Low, the compressor will operate by the set mode. When the air capacity is set auto fan, the air capacity will be adjusted by the temperature. Č. Enhanced operation Enhanced operation will continue for 15 minutes. Enhanced operation will finish if the operation is off or after 15 minutes. Enhanced operation will finish when the status be changed.
Haier air conditioner Edition: 20070116 After compressor starts, it’s not on the low load protection within 3 minutes. 4.3ˊNo enhanced function for fan and defrosting mode. č.Silence operation Send silence operation signal to outdoor unit. 5.1 Heating in the silence mode When compressor is on, air capacity is SSLO. When compressor is off, air capacity is SSLO within 20 seconds, and then it changes to be tenuity. 5.2 Cooling in the silence mode Air capacity is SSLO. 5.
Haier air conditioner Edition:20070116 7.3 Timer ON/OFF The executing order is based on the direction from the board. Đ . Sleep operating 8.1 During cool/ dry operation, the fixed temperature will rise by 1ć after it operates for 1 hour. After another hour the temperature will rise by another 1ć. After 6 hours, the unit is off. 8.2 During heat-making operation, the fixed temperature will rise by 2ć after 1 hour. After another 2 hours the temperature will rise by 2ć.
Haier air conditioner Edition:20070116 When the system switch from other mode to auto mode, if the operation status change (i.e. first determine and then operation), it will stop for 3 minutes and then determine temperature based on the indoor ventilation temperature. 9.
Haier air conditioner Edition:20070116 Heat exchange temperature sensor format: Fixed number B =3700 R (25 degree) =10KO In Cool\Dry operation mode, the unit performs low load protection operating according to Heat exchange temperature as following figure show. Low load protection control When it is on running-in process, low load protection controlling will be ignored. After enhanced cool operation start, release temporarily the low load protection control for 3 minutes. (THLH[3ˈ2ˈ1ˈ0]= 7ć ˈ4.6ćˈ2.
Haier air conditioner Edition: 20070116 High load protection activities are limited twice within 30 minutes, and then high load protection starts to be alarming. When Heat exchange temperature doesn’t reach "THHEAT[2]", the unit will return to state of normal temperature area control . The lesser value of High load frequency and area frequency is used for the operation data. Ēċ .
Haier air conditioner Edition: 20070116 ĒĎ . Error list record It indicates nothing if error code has not is recorded. Fault signal show for 10s to auto off. Remote control only receives the ‘off’ signal. Based on the ‘on/off’ or off signal of remote control, the error list will stop show. Have component of EEPROM, after power on again, the list will be recorded. Ēď. Special function 1. Indoor unit single operating a.
Haier air conditioner Edition: 20070116 2. Rating operating ķrating cool: a. G code enter condition˖high speed coolˈset temp. is 16ćˈpress temperature “-” key and set key together, enter mode after resound 2 times. b. then operate as following: Enter rated frequency operation mode; panel shown cool status; in communication rated shown. c. Exit condition˖Exit rated operate mode and enter remote control set status after received remote control signal. ĸ middle capacity: a.
Haier air conditioner Edition: 20070116 in 7sˈresound 7 times. b. Then operation as following program: Enter min capacity rated frequency operation; panel show cool status; have ration in communication. Enter rated frequency operation; Panel show cool status; have ration in communication. c. Exit condition˖Exit rated operate mode and enter remote control set status after received remote control signal. ĒĐ.
Haier air conditioner F6 Ambient temperature Sensor fault F7 F8 Heat exchange Sensor Fan unusual start F9 F10 F11 PFC protection Cool overload Compressor rotor circuit fault F12 F13 Outdoor EEPROM error Compressor forced switching failure F14 F15 Fan hall element fault Fan IPM overheat F16 F17 Fan over current Single-chip microcomputer ROM badly F18 Power supply over voltage protection F19 Power supply under voltage protection F20 Pressure protection F21 Defrosting temperature Sensor unus
Haier air conditioner Edition: 20070116 15s panel indicator extinguish, failure list express mode be canceled. Previous alarm information sent to display panel to indicate operating status. After 10s, cancel fault indicator (fault list indicator show for 10s only). During showing the fault status, don’t receive other signal. In normal mode, nothing is shown only buzzer sound. ĒĒ Air deflector control 20.1 Vertical swing 20.1.1 During power on, the entire output parts act along close direction. 20.1.
Haier air conditioner Edition: 20070116 measure standard position for enter cool /heat mode. When operate starting, alarming to keep current position. Received ventilated direction command delay 1s processing Setting position range Cool/dry: Heat: Pulse scope 45 degree Pulse scope 60degree During operating in closed cycle, it will move into open direction. Swing-blade operating stop, keep the last output phase of excitation (1 phase); when unit operating stop (all close), all of 4 phase close.
+DLHU DLU FRQGLWLRQHU (GLWLRQ +RUL]RQWDO VZLQJ :KHQ SRZHU RQ V\VWHP DOO RI WKH RXWSXW DFW DORQJ WKH FORVH GLUHFWLRQ DQG WKHQ WR PLGGOH SRVLWLRQ ,Q WKH VHW SRVLWLRQ GXH WR SRZHU UHVWRUH DQG LQLWLDOL]DWLRQ WKH LQLWLDO YDOXH LV DW WKH FHQWUDO YHUWLFDO SRVLWLRQ VWDQGDUG SRVLWLRQ 'XULQJ VZLQJ ORXYHU VWRS RSHUDWLQJ EDVHG RQ WKH IDQ GLUHFWLRQ DQG LWV SRVLWLRQ LV WKH UHPRWH FRQWURO VHW SRVLWLRQ 2SHUDWLQJ PRGH IRU WKH YHQWLODWLRQ S
Haier air conditioner Edition: 20070116 4. Thermistor resistance chart Room temperature sensor Temp. (ć) R (KO) Power Input (V) -20 -19 281.34 263.56 0.33 0.35 -18 -17 247.84 231.66 0.37 0.40 -16 -15 217.35 204.02 0.42 0.45 -14 -13 191.61 180.04 0.47 0.50 -12 -11 -10 169.24 159.17 149.77 0.53 0.56 0.59 -9 -8 140.99 132.78 0.62 0.65 -7 126.11 0.69 -6 117.93 0.73 -5 111.22 0.76 -4 104.93 0.80 -3 98.04 0.84 -2 93.52 0.88 -1 0 88.35 83.50 0.92 0.97 1 2 78.94 74.
Haier air conditioner Edition: 20070116 19 30.72 1.97 20 21 29.25 27.85 2.00 2.09 22 23 24 26.54 25.30 24.12 2.15 2.21 2.27 25 26 23.00 21.94 2.33 2.38 27 28 20.94 19.99 2.44 2.50 29 30 19.09 18.23 2.56 2.62 31 17.42 2.67 32 16.65 2.73 33 15.92 2.78 34 15.22 2.84 35 36 14.56 13.93 2.89 2.95 37 38 13.04 12.77 3.00 3.05 39 12.23 3.10 40 41 11.71 11.22 3.15 3.20 42 43 10.76 10.31 3.25 3.30 44 45 9.89 9.46 3.35 3.39 46 47 9.10 8.74 3.44 3.48 48 8.39 3.
Haier air conditioner Edition: 20070116 63 4.68 4.05 64 65 4.51 4.35 4.08 4.11 66 67 68 4.13 4.04 3.90 4.13 4.16 4.18 69 70 3.76 3.63 4.21 4.23 71 72 3.50 3.38 4.25 4.28 73 74 3.26 3.15 4.30 4.32 75 3.04 4.34 76 2.94 4.36 77 2.84 4.38 78 2.74 4.40 79 80 2.65 2.56 4.42 4.43 Indoor pipe sensor&outdoor ambient sensor, defrosting sensor Temperature(ć) R(KO) Power Input(V) -20 -19 90.79 85.72 0.90 0.95 -18 80.96 0.99 -17 76.51 1.04 -16 72.33 1.08 -15 68.41 1.
Haier air conditioner Edition: 20070116 1 29.84 2.01 2 3 28.22 26.88 2.07 2.13 4 5 6 25.61 24.41 23.27 2.19 2.25 2.31 7 8 22.20 21.18 2.37 2.43 9 10 20.21 19.30 2.49 2.54 11 12 18.43 17.61 2.60 2.56 13 16.83 2.72 14 16.09 2.77 15 15.38 2.83 16 14.71 2.88 17 18 14.08 13.48 2.93 2.99 19 20 12.90 12.38 3.04 3.09 21 11.64 3.14 22 23 11.34 10.87 3.19 3.24 24 25 10.43 10.00 3.29 3.33 26 27 9.59 9.21 3.38 3.42 28 29 8.84 8.48 3.47 3.51 30 8.15 3.55 31 7.
Haier air conditioner Edition: 20070116 45 4.58 4.07 46 47 4.42 4.26 4.10 4.12 48 49 50 4.11 3.97 3.83 4.15 4.17 4.20 51 52 3.70 3.57 4.22 4.24 53 54 3.45 3.33 4.26 4.28 55 56 3.22 3.11 4.31 4.33 57 3.00 4.35 58 2.90 4.37 59 2.81 4.38 60 2.72 4.40 61 62 2.63 2.54 4.42 4.44 63 64 2.45 2.36 4.45 4.47 65 2.30 4.48 66 67 2.23 2.15 4.50 4.51 68 69 2.09 2.03 4.53 4.54 70 71 1.96 1.90 4.55 4.57 72 73 1.85 1.79 4.58 4.59 74 1.73 4.60 75 1.68 4.61 76 1.
Haier air conditioner Edition: 20070116 OUTDOOR discharge -temperature sensor R80ć=50K¡±3% B25/80ć=4450K±3% temperature max Resistance normal, Resistance min Resistance ¥˄t˅ (ć) (Kȍ) (Kȍ) (Kȍ) (ć) -30 14646.0505 12061.7438 9924.4999 -2.96 2.45 -29 13654.1707 11267.8730 9290.2526 -2.95 2.44 -28 12735.8378 10531.3695 8700.6388 -2.93 2.44 -27 11885.1336 9847.7240 8152.2338 -2.92 2.43 -26 11096.6531 9212.8101 7641.8972 -2.91 2.42 -25 10365.4565 8622.8491 7166.
Haier air conditioner Edition: 20070116 1 2045.9191 1784.3336 1554.7931 -2.52 2.21 2 1932.0242 1687.8144 1473.1460 -2.50 2.20 3 1825.0899 1597.0431 1396.2333 -2.48 2.19 4 1724.6540 1511.6468 1323.7551 -2.47 2.17 5 1630.2870 1431.2787 1255.4324 -2.45 2.16 6 1541.5904 1355.6163 1191.0048 -2.43 2.15 7 1458.1938 1284.3593 1130.2298 -2.41 2.14 8 1379.7528 1217.2282 1072.8813 -2.40 2.13 9 1305.9472 1153.9626 1018.7481 -2.38 2.12 10 1236.4792 1094.
Haier air conditioner Edition: 20070116 41 262.0206 242.6161 224.4465 -1.76 1.64 42 250.2676 232.0436 214.9529 -1.74 1.63 43 239.0983 221.9825 205.9065 -1.71 1.61 44 228.4809 212.4060 197.2844 -1.69 1.59 45 218.3860 203.2887 189.0648 -1.67 1.57 46 208.7855 194.6066 181.2273 -1.65 1.55 47 199.6531 186.3369 173.7524 -1.63 1.54 48 190.9639 178.4584 166.6217 -1.60 1.52 49 182.6945 170.9508 159.8181 -1.58 1.50 50 174.8228 163.7951 153.3249 -1.56 1.
Haier air conditioner Edition: 20070116 81 49.7063 48.2057 46.7083 -0.85 0.85 82 47.9835 46.4842 44.9911 -0.89 0.89 83 46.3286 44.8323 43.3452 -0.93 0.92 84 44.7385 43.2468 41.7672 -0.96 0.95 85 43.2105 41.7248 40.2540 -1.00 0.99 86 41.7386 40.2604 38.7996 -1.03 1.02 87 40.3241 38.8545 37.4048 -1.07 1.06 88 38.9643 37.5045 36.0668 -1.11 1.09 89 37.6569 36.2078 34.7831 -1.14 1.13 90 36.3996 34.9622 33.5513 -1.18 1.16 91 35.1903 33.7653 32.
Haier air conditioner Edition: 20070116 120 14.1376 13.1879 12.2909 -2.41 2.27 121 13.7294 12.7955 11.9144 -2.45 2.31 122 13.3347 12.4165 11.5510 -2.50 2.35 123 12.9531 12.0503 11.2003 -2.54 2.39 124 12.5840 11.6965 10.8617 -2.58 2.43 125 12.2270 11.3545 10.5348 -2.63 2.47 126 11.8817 11.0240 10.2191 -2.68 2.51 127 11.5475 10.7046 9.9142 -2.72 2.55 128 11.2242 10.3957 9.6197 -2.77 2.59 129 10.9112 10.0970 9.3352 -2.81 2.63 130 10.6084 9.
Haier air conditioner Edition: 20070116 5.
Haier air conditioner With this malfunction, LED1 F22 on the outdoor mainboard blinks 3 times.
Haier air conditioner E1: Room temperature sensor failure Edition: 20070116 CN8 E2: Heat-exchange sensor failure Firstly check whether No Terminal CN8(CN6) on the indoor mainboard Pull out the terminals on the indoor mainboard and reinsert them. contact well or not? Yes Pull the sensor out of the mainboard 1) Measure the value of resistance between its two jumpers Yes 2) Measure the temperature at the room temperature sensing head.
Haier air conditioner Edition: 20070116 F21: Frost-removing temperature sensor failure CN10 F25: Exhaust temperature sensor failure CN11 F6: CN9 Ambient temperature sensor failure Firstly check whether Terminal CN10 (or CN11, or CN9) on No the out door mainboard contact well or not? Pull out the terminals on the outdoor mainboard and reinsert them.
+DLHU DLU FRQGLWLRQHU (GLWLRQ ( &RPPXQLFDWLRQ IDXOW EHWZHHQ WKH LQGRRU DQG RXWGRRU XQLWV 5HVWDUW WKH D F DQG LW EHFRPHV QRUPDOO\
+DLHU DLU FRQGLWLRQHU ,I ERWK 9$& DQG '& DUH DYDLODEOH PHDVXUH WKH YROWDJH ,I /(' EOLQNV LQWHUUXSWHGO\ PHDVXUH WKH YROWDJH EHWZHHQ -XPSHUV DQG RI ,& RQ DFURVV -XPSHUV DQG RI ,& RQ WKH RXWGRRU PDLQERDUG ZLWK D PXOWLPHWHU 1R H KH 63'8 ,3'8 +7 PRGXOH LV GDPDJHG SODFH LW ZLWK D QHZ RQH (GLWLRQ &KHFN ZKHWKHU '& LV WKH LQGRRU PDLQERDUG ZLWK D PXOWLPHWHU ,I WKH YROWDJH DYDLODEOH YDULHV EHWZHHQ DQG 9 '&
Haier air conditioner Edition: 20070116 F11: The malfunction of the compressor’ rotor circuit Within 3 minutes after the machine is supplied with power and turned on with 1. The wiring of compressor is the remote controller, the outdoor unit Yes stops shortly after startup, and the incorrect or the connection is compressor will start up again 10 poor; seconds after the machine stops. The 2. The compressor is damaged above process repeats again and again.
Haier air conditioner Edition: 20070116 F4: Overheat protection for exhaust temperature 1) The cryogen may have been leaked during Electrify the machine again and turn it on with installation, or there may the remote controller, then measure the Yes temperature at the exhaust temperature sensor of the compressor on the outdoor unit be leakage in the piping system.
Haier air conditioner Edition: 20070116 F22: AC electricity protection Electrify the machine again and turn it on with the remote controller. If Yes malfunctions are reported before or The IPM is damaged upon the compressor being started up. No The compressor is started normally, but malfunctions are reported after it Yes has run for some time. Check the Repair the power supply power supply.
Haier air conditioner Edition: 20070116 F1: The protection of IPM Electrify the machine again and turn it IPM Module might be poorly on with the remote controller, then Yes measure temperature on the module radiated and need to be recoated with heat conducting paste and radiator and decide whether it is too reinstalled. high. No With a multimeter, test whether there is diode characteristic between the No three terminals U/V/W and whether IPM Module is damaged and needs replacing.
Haier air conditioner Edition: 20070116 E9: High work-intense protection Electrify the machine again and turn it on with the remote controller, then Yes check whether the wind temperature is Check room temperature sensor. Methods is like E1 below 65ć and the malfunction is reported after the machine has run for some time? No Yes Check whether the indoor unit blows poorly due to blocked filters or poor 1) Clean the filters 2) Reinstall the fan.
Haier air conditioner E4: Indoor EEPROM error Replace the PCB of indoor unit F12: Outdoor EEPROM error Replace the PCB of outdoor unit - 51- Edition: 20070116
HSU-09/12HR03/R2(DB) 7.3.2 Service diagnosis Indoor fan motor malfunction Indoor Display Method of Malfunction Detection Malfunction Decision Conditions E14 The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor operation when the detected rotation feedback singal don’t receiced in 2 minutes Ƶ Operation halt due to breaking of wire inside the fan motor .
Haier air conditioner Edition: 10061116 F3: Communication fault between the IPM and outdoor PCB 1, Check whether Terminal CN7 1, Pull out and reinsert the on the outdoor mainboard, CN10 Yes on IPM module are well inserted. terminals. 2, Replace connected wire 2, Check whether the connected wire between IPM and outdoor is well No Electrify the machine again and turn it on, check whether the voltage between 1 and 4of Terminal CN7 is about 12V DC Yes Replace the outdoor IPM module with a new one.
Haier air conditioner Edition: 20070116 F19: Power voltage is too high or low Check whether the voltage Yes between P and N of Terminal The IPM module is damaged and needs replacing CN7 of the outdoor is below 120vDC or up 400vDC. No Check whether there is voltage No of 187-260VAC between Check power supply Positions 1 and 2 on the terminal block of the outdoor unit.
Haier air conditioner Edition: 20070116 Other malfunctions: With the machine electrified, the unit cannot open If there is no response after the emergency button is pressed down, shoot the trouble as follows The power supply damage, and Check whether the voltage No between Positions 1 and 2 on the the power cables might be broken terminal of the indoor unit is 230V AC. Yes Check whether the FUSE of the Yes indoor mainboard is burned or broken.
Haier air conditioner 6. Performance curves diagram 6.
Haier air conditioner Edition: 20070116 6.2.1 Cooling capacity-temperature curves HSU-09HSA03/R2(DB) Cooling value - Temperature table Indoor temp. Outdoor temp.
Haier air conditioner Edition: 20070116 HSU-12HSA03/R2(DB) Cooling value - Temperature table Indoor temp. Outdoor temp.
Haier air conditioner Edition: 20070116 6.2.2 Heating capacity-temperature curves HSU-09HSA03/R2(DB) Heating capacity - Temp. curves Outdoor temp. Indoor temp. (Humidity 46%) 20/12ć 20/14.
Haier air conditioner Edition: 20070116 HSU-12HSA03/R2(DB) Heating capacity - Temp. curves Outdoor temp. Indoor temp. (Humidity 46%) 20/12ć 20/14.
Haier air conditioner Edition: 20070116 6.3 Air outlet temp.-ambient temperature curves HSU-09HSA03/R2(DB) Air outlet temp. - Ambient temp. table Indoor temp. DB/WB 18ć 20ć Outdoor temp. (Humidity 46%) 25ć 32ć 35ć 40ć 18/12ć 9.30 9.69 9.81 10.10 12.10 12.66 11.52 10.67 18/14ć 20/15ć 9.47 9.74 10.10 10.64 12.16 12.85 11.77 11.19 10.29 10.64 10.91 11.65 13.46 13.97 12.82 12.39 22/16ć 10.74 11.20 11.68 12.31 14.19 15.00 13.51 12.80 25/18ć 11.63 12.14 12.52 12.
Haier air conditioner Edition: 20070116 HSU-12HSA03/R2(DB) Air outlet temp. - Ambient temp. table Indoor temp. Outdoor temp. (Humidity 46%) 25ć 32ć 35ć 40ć DB/WB 18/12ć 18ć 20ć 43ć 46ć 7.63 7.94 8.05 8.28 9.92 10.15 9.45 8.75 18/14ć 7.77 7.98 8.43 8.92 10.17 10.63 9.65 9.18 20/15ć 22/16ć 8.38 8.72 8.95 9.55 11.03 11.54 10.51 10.00 8.81 9.18 9.56 10.09 11.63 12.30 11.08 10.50 25/18ć 9.65 9.95 10.27 10.60 12.18 12.82 11.84 11.27 27/19ć 10.18 10.50 11.
Haier air conditioner Edition: 20070116 6.4.1 Cooling discharge pressure curves HSU-09HSA03/R2(DB) Cooling discharge pressure table Outdoor temp. (Humidity 46%) Indoor temp.
Haier air conditioner Edition: 20070116 HSU-12HSA03/R2(DB) Cooling discharge pressure table Outdoor temp. (Humidity 46%) Indoor temp.
Haier air conditioner Edition: 20070116 6.4.2 Cooling suction pressure curves HSU-09HSA03/R2(DB) Cooling suction pressure table Outdoor temp. (Humidity 46%) Indoor temp.
Haier air conditioner Edition: 20070116 HSU-12HSA03/R2(DB) Cooling suction pressure table Outdoor temp. (Humidity 46%) Indoor temp.
Haier air conditioner Edition: 20070116 6.4.3 Heating discharge pressure curves HSU-09HSA03/R2(DB) Heating discharge pressure table Outdoor temp. (Humidity 46%) Indoor temp.
Haier air conditioner Edition: 20070116 HSU-12HSA03/R2(DB) Heating discharge pressure table Outdoor temp. (Humidity 46%) Indoor temp.
Haier air conditioner Edition: 20070116 6.4.4 Heating suction pressure curves HSU-09HSA03/R2(DB) Heating suction pressure table Outdoor temp. (Humidity 46%) Indoor temp.
Haier air conditioner Edition: 20070116 HSU-12HSA03/R2(DB) Heating suction pressure table Outdoor temp. (Humidity 46%) Indoor temp.
Haier air conditioner Edition: 20070116 6.5 Sensible cooling value-temperature curves HSU-09HSA03/R2(DB) Sensible cooling value - Temperature table Indoor temp. DB/WB 18ć 20ć Outdoor temp.
Haier air conditioner Edition: 20070116 HSU-12HSA03/R2(DB) Sensible cooling value - Temperature table Indoor temp. DB/WB 18/12ć 18ć 20ć Outdoor temp.
Haier air conditioner Edition: 20070116 6.6 Power consumption-temp. Curves HSU-09HSA03/R2(DB) Power consumption value - Temp. table Indoor temp. DB/WB 18ć 20ć Outdoor temp.
Haier air conditioner Edition: 20070116 HSU-12HSA03/R2(DB) Power consumption value - Temp. table Indoor temp. DB/WB 18/12ć 18ć 20ć Outdoor temp.
Haier air conditioner Edition: 20070116 6.
Haier air conditioner Edition: 20070116 6.
Haier air conditioner COMPRESSOR: C-6RZ092H1A Edition: 20070116 HSU-12HSA03/R2(DB) SERIAL NUMBER 1 2 3 4 5 6 7 FREQUENCY 20 30 40 50 60 70 78 455 659 821 1065 1309 1760 1877 INPUT POWER INPUT POWER ,1387 32:(5 SERIAL NUMBER FREQUENCY INPUT POWER 1 20 2 30 3 40 4 50 5 60 6 70 7 78 1293 1635 2387 3146 3533 4237 4554 ,1387 32:(5 ,1387 32:(5
Haier air conditioner 7.
Haier air conditioner Edition: 20070116 :,5,1* ',$*5$0 2) 287'225 81,7 :$51,1* &$87,21 &2035(6625 '21 7 728&+ &$3$&,725 (9(1 $)7(5 3/8* 2)) '$1*(5 2) (/(&75,& 6+2&.
A B C D R7 4.7K 4.7K R4 R69 0.01UF C6 1K 10K 1 N1 2SC2412 R5 R8 10K 2200uF/ 35V E1 330 +5V IC6 IC5 1 IC3 0.1UF C1 +12V R44 D5 1N4007 0.001UF 1K 0.01UF 1K R39 10K R17 100 C15 R58 R51 SW1-1 7805 E4 0.01UF C26 0.1UF C4 +5V R42 330K TLP371 C5 0.1UF 10K 10K R40 +5V 2.2K ĭ3 R41 LED1 0.1UF C25 +5v C21 0.01UF TLP421 470uF/25V 3 E5 +5V 1K 10K R61 R46 R45 100uF/16V 0.
Haier air conditioner Outdoor Unit - 81 - Edition: 20070116
Haier air conditioner Edition: 20070116 Installation Manual of Room Air Conditioner Read this manual before installation Explain sufficiently the operating means to the user according to this manual. Necessary Tools for Installation 1.Driver 2.Hacksaw 3.Hole core drill 4.Spanner(17,19 and 26mm) 5.Torque wrench(17mm,22mm,26mm) 6.Pipe cutter 7.Flaring tool 8.Knife 9.Nipper 10.Gas leakage detector or soap-and-water solution 11.Measuring tape 12.
319.5 Edition: 20070116 256 256 Haier air conditioner 113.5 140 500 583 140 140 Floor fixing dimensions of the outdoor unit (Unit:mm) 113.5 140 Floor fixing dimensions of the outdoor unit (Unit:mm) Floor fixing dimensions of the outdoor unit (Unit:mm) HSU-09HSA03/R2(DB) HSU-12HSA03/R2(DB) Fixing of outdoor unit 500 HSU-22HSA03/R2(DB) HSU-18HSA03/R2(DB) Fix the unit to concrete or block with bolts( 10mm) and nuts firmly and horizontally.
Haier air conditioner Edition: 20070116 Indoor unit 1.Fitting of the Mounting Plate and Positioning of the wall Hole When the mounting plate is first fixed 1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail. 2.
Haier air conditioner Edition: 20070116 Indoor unit 3.Installation of the Indoor Unit Drawing of pipe Rear piping Draw pipes and the drain hose, then fasten them with the adhesive tape Left Left-rear piping In case of left side piping, cut away, with a nipper, the lid for left piping. In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear piping which is marked on heat insulation materials. 1.
Haier air conditioner Edition: 20070116 Indoor unit When connecting the cable after installing the indoor unit 1. Insert from outside the room cable into left side of the wall hole, in which the pipe has already existed. 2. Pull out the cable on the front side, and connect the cable making a loop. When connecting the cable before installing the indoor unit Insert the cable from the back side of the unit, then pull it out on the front side.
Haier air conditioner Edition: 20070116 Outdoor unit 1.Installation of Outdoor Unit Install according to Drawing for the installation of indoor and outdoor units 2.Connection of pipes To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius should be 30 to 40 mm or longer. Connecting the pipe of gas side first makes working easier. The connection pipe is specialized for R410A. The max vertical distance between the indoor unit and the outdoor unit is 5 m.
Haier air conditioner Edition: 20070116 Outdoor unit 3-way valve Gas Side 12.7mm(1/2") 5.Purging Method:To use vacuum pump 2-way valve Liquid Side 6.35mm(1/4") Detach the service port's cap of 3-way valve, the Gaugemanifold(for R410A) valve rod's cap for 2-way valve and 3-way's, connect the service port into the projection of charge hose Anti countercurrent joint (Iow) for gaugemanifold.
Haier air conditioner Edition: 20070116 1.Power Source Installation The power source must be exclusively used for air conditioner. (Over I0A) In the case of installing an air conditioner in a moist place, please install an earth leakage breaker. For installation in other places, use a circuit breaker as far as possible. 2.Cutting and Flaring Work of Piping Pipe cutting is carried out with a pipe cutter and burs must be removed. After inserting the flare nut, flaring work is carried out.