Submittals

Tempo Submittal
Rev. Feb. 2021
Cooling Performance
Rated Cooling Capacity 12,000 BTU
Cooling Capacity Range 4,100~13,000 BTU
Rated Power input 1,100 W
SEER 18.0
EER 11.0
Heating Performance
Rated Heating Capacity 12,000 BTU
Heating Capacity Range 4,500~13,000 BTU
HSPF 10.0
12,000 BTU 16 SEER Wall Mount Single-Zone Heat Pump System
1U12TE2VHA / AW12TE2VHA
CUS
Intertek
For more information visit us:
www.Haierductless.com
www.Haierductlesshelp.com
Electrical Requirement
Power Supply
208/230V, 1 Phase,
60 HZ
Operating Voltage Range 187~253 VAC
Recommended Fuse/Breaker Size 15A
MCA 12A
Connecting cable to indoor units must be 14/4 AWG unshielded stranded
copper. Cable must be ran continuous, without splicing.
Job Name: __________________________________
Purchaser: __________________________________
Submitted To: _______________________________
Construction: _______________________________
Reference: __________________________________
Approval: ___________________________________
Date: ______________________________________
Submitted By: _______________________________
Unit: _______________________________________
Drawing #: __________________________________
Accessories
Controller Model/Part Number Note
Ships with
Standard Remote Control
(WJ01X24721)
Compatible
Controllers
Simplied Wired Controller
(QACT17A)
Requires
WK-B kit
Programmable Wired Controller
(YR-E16B)
Requires
WK-B kit
WiFi Module N/A (Embedded)
Wind Bae QAWB41A
Operating Range
Cooling with Wind Bae -4~115°F (-20~46°C)
Cooling Without Wind Bae 23~115°F (-5~46°C)
Heating -4~75°F (-20~24°C)
Pipe Length
Minimum Pipe Length 6 ft
Maximum Pipe Length 66 ft
Maximum Pipe Height Dierence 33 ft
Flare Connections
Liquid 1/4”
Vapor 3/8”