3 SEER 1.5 to 3.0 Ton HR18D2VAR HR24D2VAR HR30D2VAR HR36D2VAR No.
! WARNING These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
TABLE OF CONTENT 1.Introduction --------------------------------------------------------------------------------------- 1 2.Nomenclature for Model Number ------------------------------------------------------------- 1 3.Specification ------------------------------------------------------------------------------------- 2 4.Unit Inspection ----------------------------------------------------------------------------------- 5 5.
1000 Nominal RPM 2 1075 3/8"[9.52] 1000 3/8"[9.52] [682* 682*725] 189[86] 205[93] [682*682*725] 172[78] 187[85] 183[83] 26 7/8"*26 7/8"*28 1/2" 26 7/8"*26 7/8"*28 1/2" 26 7/8 "*26 7/8"* 28 1/ 2" Approx Shipping Weight - Lbs (kg) [ 616 *616*683] [616 *616*683] [616*616*683] 141.34[4000] 24 1/4"*24 1/4"*26 7/8" Net Weight - Lbs (kg) W*D*H 1/4 1/8 3/4"[19.05] 1.4 0.86 3/4"[19.05] 107.77[3050] 61 53.5 10.1 25 20 8.0 14.0 197 - 253 208/230 60Hz 1PH HR30D2VAR 10.
D W H Figure 1 Table 2: System Capacity cooling Outdoor Indoor Indoor fan speed ARI data of indoor Cooling Capacity with different outdoor temperature Capacity SEER CFM 80 85 90 95 100 105 110 115 17237 16490 16712 15980 21825 21488 21150 HR18D2VAR HB2400VD1M20 M 17000 13 670 19210 19197 18020 17000 HR24D2VAR HB2400VD1M20 H 22500 13 900 25425 24683 23850 22500 22162.
Heat Pump Refrigerant Circuit Figure 2 Cooling DISCHARGE TEMP. SENSOR SERVICE PORT SERVICE VALVE REVERSING VALVE HIGH PRESSURE LOW PRESSURE ACCUMULATOR SERVICE PORT SERVICE PORT DEFROSED SENSOR CHECK VALVE ORIFICE DRIER(optional) INDOOR COIL DISTRIBUTOR Heating CHECK VALVE ORIFICE SERVICE VALVE SERVICE PORT SERVICE VALVE CONDENSER EVAPORATOR COMPRESSOR OUTDOOR COIL DISTRIBUTOR DISCHARGE TEMP.
4.UNIT INSPECTION This product has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully. If damage is found, report immediately to the transportation agency. 5.EQUIPMENT PROTECTION FROM ENVIRONMENT The metal parts of the unit may be subject to rust or corrosion in adverse environmental conditions. This oxidation could shorten the unit life.
Provide a level concrete slab. To prevent transmission of noise or vibration, slab should not be connected to building structure. Some sort of sound-absorbing material should be placed between the condenser and the slab. A good material to use is rubber and cork pad. For rooftop application, make sure the building construction can support the weight and that proper consideration is given to the weather-tight integrity of the roof. The condensing unit contains moving parts and can vibrate.
OUTDOOR UNIT ADDITIONAL SUCTION LINE OIL TRAP FOR EACH 20 FOOT RISE OF PIPE PITCH SUCTION LINE TOWARD OUTDOOR UNIT 1/2" FRO EVERY 10' OF LINE INDOOR UNIT ABOVE OR LEVEL TO OUTDOOR UNIT OUTDOOR UNIT LIQUID LINE 70' LIQUID LINE MAX. SUCTION LINE OIL TRAP WHEN INDOOR UNIT IS 4 FEET OR MORE BELOW OUTDOOR UNIT INDOOR UNIT A INDOOR UNIT BELOW OUTDOOR UNIT 6' B-1 INVERTED LOOP LIQUID LINE INDOOR UNIT INDOOR UNIT 50' MAX.
Refrigerant Line Sizing Check the following table (Table 3) for correct suction and liquid line sizes for any combination of the unit size and the maximum refrigerant line length. Unit Size (Ton) Refrigerant Line Length (Ft) 0 - 24 25 - 49 50 - 74 Line Outside Diameter (In) Suction Liquid Suction Liquid Suction Liquid SEER 1.5 3/4 3/8 3/4 3/8 7/8 1/2 13 2.0 2.5 3/4 3/4 3/8 3/8 3/4 3/4 3/8 3/8 7/8 7/8 1/2 1/2 13 13 3.
1.Tubing should be cut square. Make sure it is round and free of burrs at the connecting ends. Clean the tubing to prevent contamination from entering the system. 2.Make sure that both refrigerant stop valves at the outdoor unit are closed. 3.Push the tubing into the fitting until it stops. This prevents flux from getting into the system. 4.Remove the cap and Schrader valve core from the service port to protect the valve seals. 5.Wrap a wet rag around the valve stub before brazing. 6.
Evacuation All new installations must be evacuated to a deep vacuum in order that all noncondensible gases and moisture are removed prior to charging the system. Air in a system causes high condensing pressure, which increases power consumption and reduces performance. The presence of moisture in a system can render it inoperable in a very short time. Proper evacuation assures a dry, uncontaminated system. Here is the recommended evacuation procedure: 1.
5 5
The condensing unit rating plate and the tables of "Physical and Electrical Specifications / Outdoor Units" (Table 1) provide pertinent data necessary for the selection of proper size electrical service and over-current protection devices. Table 6 provides data on the minimum copper wire size as a function of supply wire length and circuit ampacity.
11.If checking the unit on the heating cycle in the wintertime, when the outdoor coil is cold enough to actuate the defrost control, observe at least one defrost cycle to make sure the unit defrosts properly. 12.Check the refrigerant charge (see Instructions under "Charging the System"). 13.Replace service port caps. Service port cores are for system access only and will leak if not tightly capped. 14.Check unit for tubing and sheet metal rattles. 15.Instruct the owner on operation and maintenance.
Symptom Possible Cause Remedy Defective four way valve Check the valve coil or replace it Power off or loose electrical connection Incorrect thermostat setting No cooling/heating Defective contactor Open circuit breaker of blown fuses Defective transformer Interconnecting low voltage wiring damage Dirty filters Indoor air blockage Blocked outdoor coil Improperly sized unit Insufficient Cooling Improper airflow /Heating Incorrect refrigerant charge Air, non-condensibles or moisture in system Incorrect v
HR18-36D2VAR YL/GR 15
Made in P.R.C.