Owner's manual

Quick Start Guide
(FoamLogix Water Flow Calibration)
1. Start the pumping unit per the
manufacture’s operating instructions.
Set pump pressure and flow to the low
end of the units intended performance
(using a calibrated Pitot, nozzle, etc.).
2. Press and hold the DISPLAY button
(
i) on the FoamLogix display until
PASS is shown, approximately 2
seconds
.
(See Figure 1.)
3. With the DISPLAY button (
i) pressed,
press the INCREASE button 4 times.
( ).
A u is shown with each INCREASE
button ( ) press.
(See Figure 2 in the
next column.)
4. Release the DISPLAY (
i) button. The
display shows CAL for 2 seconds in-
dicating the calibration mode has been
entered. (See Figure 3 in the next
column.)
5. The display shows the water flow rate.
Refer to the complete product manual
for the rate unit settings; i.e., GPM,
LPM, etc. (See Figure 4.)
Calibration
DD
DD
D
DD
DD
D
DD
DD
D
DD
DD
D
Figure
1
Figure
2
Figure
4
Figure
3
DD
DD
D
THIS QUICK START GUIDE IS ONLY INTENDED AS A BRIEF OVERVIEW TO THE
OPERATION OF THE FOAMLOGIX 2.1A, 3.3 AND 5.0 SYSTEMS AND IS NOT
INTENDED TO BE A REPLACEMENT FOR THE INSTALLATION / OPERATION
MANUAL (HALE P/N: 029-0020-74-0 OR 029-0020-68-0) PROVIDED WITH EACH
SYSTEM. ALSO AVAILABLE ON-LINE – WWW.CLASS1.COM.

Summary of content (2 pages)