Specification

12 5/16"
313mm
FINISHED FLOOR
HANGER BRACKET
1 3/8"
35mm
1 3/8"
35mm
5 3/4"
146mm
5 3/4"
146mm
E
F
L
C
27"
686mm
ADA
REQUIREMENT
13 7/8"
352mm
18 3/8"
467mm
21 3/8"
543mm
25"
635mm
31"
787mm
5/16" (8mm) DIA. (5 HOLES)
2 1/2"
64mm
3 1/2"
89mm
4 1/2"
114mm
2 7/16"
63mm
5"
127mm
10"
254mm
11/16"
18mm
2 9/16"
65mm
7 1/4"
185mm
A
D
B
E
6 1/4"
159mm
8"
203mm
1 1/2"
38mm
C
4 9/16"
116mm
6 3/4"
172mm
7"
178mm
7"
178mm
O
7/16"
11mm
MOUNTING HOLES
(6)
15"
381mm
3 3/16"
82mm
52 1/16"
1323mm
17 7/8"
454mm
3 9/16"
90mm
18 1/2"
471mm
2 5/8"
67mm
18 7/8"
479mm
31 13/16"
808mm
RIM
HEIGHT
33"
838mm
ORIFICE
HEIGHT
39 1/16"
991mm
ACTIVATION
SENSOR
Printed in the U.S.A.
®
Page 2
REDUCE HEIGHT BY 3” FOR INSTALLATION OF CHILDRENS ADA COOLER
LEGEND:
A = Recommended Water Supply Location. Shut-off valve (not furnished) to accept
3/8” O.D. unplated copper tube. Up to 3” (76mm) maximum out from wall.
B = Recommended Waste Outlet location. To accommodate 1-1/4” nominal drain.
Drain stub 2” (51mm) out from wall.
C = 1-1/4” Trap (not furnished).
D = Electrical Supply (3) Wire Recessed Box Duplex Outlet.
E = Insure proper ventilation by maintaining 6” (152mm) minimum clearance from
cabinet louvers to wall.
F = 7/16” (11mm) Bolt Holes for fastening to wall.
**New Installations Must Use Ground Fault Circuit Interrupter (GFCI).
Job Name: ____________________________________
Model: _____________________________ Qty. ______
Contact: ______________________________________
Approval Signature: _____________________________
Notes:
Model HTHB-HAC8WF and HTHB-HACDWF
Filtered Single HAC Cooler with
Hydroboost
®
Bottle Filler
FRONT VIEW SIDE VIEW
OPERATING PRESSURES
Supply water - 105 psi maximum
Minimum 40 psi supply line pressure required
in special circumstances where both sides of
bi-level are in use simultaneously to ensure
adequate stream height. Use of water lter in
this situation is not recommended.
ELECTRICAL
Hydroboost
®
station equipped with electric cord
and three-prong molded rubber plug for use with
15-amp minimum receptacle. Rated at 115 volt,
60 Hz, single phase.
NOTE: A service stop (not included) must be installed at
the water inlet line.
NOTE: P-Trap (not supplied) to be installed per local
building code.