Stove User's Manual

Hampton H200 Cast Freestanding Woodstove
11
FLOOR PROTECTION
NOTE: In Canada, oor protection
must extend 18" (450mm) to
the front and 8" (200mm) to
each side and back of the
stove.
Minimum Overall Depth (Y) of Floor Protector
Residential Residential Mobile Home Alcove
Unit "C" Vent Close Clearance Close Clearance
Y Z Y Z Y Z Y Z
H200 (US) 43" 6" (152 mm) 43" 6" (152 mm) 43" 6" (152 mm) 43" 6" (152 mm)
(1092 mm) (1092 mm) (1092 mm) (1092 mm)
H200 (Canada) 45" 8" (203 mm) 45" 8" (203 mm) 45" 8" (203 mm) 45" 8" (203 mm)
(1143 mm) (1143 mm) (1143 mm) (1143 mm)
INSTALLATION
Minimum Overall Width (X) of Floor Protector for all installations:
H200 36" (914 mm) - US
40" (1016 mm) - Canada
How To Determine If Alternate Floor Protection Materials Are Acceptable
The speci ed oor protector should be 3/8"
(18mm) thick material with a K - factor of
0.84.
The proposed alternative is 4" (100mm) brick
with a C-factor of 1.25 over 1/8" (3mm) mineral
board with a K-factor of 0.29.
Step (a):
Use formula above to convert speci cation
to R-value.
R = 1/k x T = 1/0.84 x .75 = 0.893.
Step (b):
Calculate R of proposed system.
4" brick of C = 1.25, therefore
Rbrick = 1/C = 1/1.25 = 0.80
1/8" mineral board of k = 0.29, therefore
Rmin.bd. = 1/0.29 x 0.125 = 0.431
Total R = Rbrick + Rmineral board =
0.8 + 0.431 = 1.231.
Step (c):
Compare proposed system R of 1.231 to
speci ed R of 0.893. Since proposed system
R is greater than required, the system is
acceptable.
DEFINITIONS
Thermal Conductance:
C = Btu = W
(hr)(ft
2
)(
o
F) (m
2)
)(K)
Thermal Conductivity:
k = (Btu)(inch) = W = Btu
(hr)(ft
3
)(
o
F) (m)(K) (hr)(ft)(
o
F)
Thermal Resistance:
R = (ft
2
)(hr)(
o
F) = (m
2
)(K)
Btu W
A combustible oor must be protected by non-combustible material
(like tile, concrete board, or certi ed to UL-1618 or as de ned by
local codes) extending beneath the heater and a minimum of 6"
from each side and minimum 16" from the front face of the stove
and minimum 6" (or the rear clearance to combustibles whichever
is smaller) from the rear of the stove.
When installed with horizontal venting, non-combustible oor
protection must beneath the ue pipe and extend 2" (51mm)
beyond each side.
A minimum of a 1/2" thick thermal oor protector with a 0.84k
factor is required when installing the standard or optional short
legs. This applies to both Canada and the US. All other require-
ments (ie. hearth size) remain the same.