User's Manual

26
D ppm
Seconds15 30 45
60
50
100
150
200
15 30 45 60
e.g. HI 9935 proportional control
Setpoint = 1600 ppm (TDS)
Measured value = 1550 ppm
Delta = 1600 - 1550 = 50 ppm
Proportional settings = ppm set to 200 and time cycle to 60 seconds
The controller will be dosing fertil-
izers to reach the desired value.
Since it is 50/200 = 25% away
from the ideal setting, it will
keep the dosing really activated
for 25% of the time over the
predetermined 60 seconds. The
terminals are hence activated for
15 seconds and off for 45 seconds until the next cycle.
0
mS
0.50
DEAD BAND
OVERDOSAGE TIMEROVERDOSAGE TIMER
OVERDOSAGE TIMEROVERDOSAGE TIMER
OVERDOSAGE TIMER
The controllers provide for an overdosage alarm system. The
operator can set the maximum amount of time that the dosage
terminals should continuously remain activated.
CONDUCTIVITY DEAD BANDCONDUCTIVITY DEAD BAND
CONDUCTIVITY DEAD BANDCONDUCTIVITY DEAD BAND
CONDUCTIVITY DEAD BAND
(HI 9923)(HI 9923)
(HI 9923)(HI 9923)
(HI 9923)
HI 9923 provides for a user-selectable DEAD BAND (see 15 -
Functional Diagram) which is deducted from the setpoint to decide the
intervention point when bleeding the system. The DEAD BAND can be
adjusted from 0 to 0.50 mS.
For example if 0.25 is dialed on the DEAD
BAND, with the setpoint adjusted to 4 mS/
cm (see 11 - Functional Diagram), the Con-
ductivity relay will bleed the system until the
reading reaches 3.75. It will then restart the bleed to correct the
conductivity at 4.25.
HI 9923 also provides for an ON/OFF pH control with a 0.1 pH
hysteresis.