User Manual

Section 1: Wiring Guide
1 Excitation + 7 No Connect
2 Sense + 8 No Connect
3 Signal + 9 Floating Ground
4 Signal - 10 Floating Ground
5 Sense - 11 Floating Ground
6 Excitation - 12 Floating Ground
EXCITATION VOLTAGE: 5 VDC
4-WIRE SENSOR
Important: 4-wire sensor jump pins 1 & 2 and 5 & 6
ATTENTION: Do not insert or remove module while the PLC is powered.
“Hot-Swapping” may result in damage to the PLC and/or the module.
6-WIRE SENSOR