Statusword
At word
14, the module returns a binary statusword where each bit indicates a state or
condition within the module. To interpret these states, note which bits are ON and use the
chart below to match each bit location to the state it represents.
For Example: If the statusword is 69 with a binary value of 0000 0000 0100 0101, bits 0,
2, and 6 are on. Bit 0 indicates an A/D conversion error, bit 2 indicates status is ON and
bit 6 indicates a shutdown error.
STATUSWORD bit positions refer to these variables:
Word # Definition
ERRORADCONVERT 0x0001/0
Millivolt return from the load cell
system is out of range for the unit.
ERRORADFAILURE 0x0002/1 Unit’s A/D converter not responding.
STATUS_ON 0x0004/2 System on or off
ERRORLOWALARM 0x0008/3 Low alarm
ERRORHIGHALARM 0x0010/4 High alarm
ERRORCONTROL_LOST 0x0020/5 Controller communication failure
ERROR_SHUTDOWN 0x0040/6 Shutdown
ERROR_RANGE 0x0080/7 Out of range value
ERROR_REC 0x0100/8 REC value over high limit
ERROR_RECMINUS 0x0200/9 REC value below low limit
ERROR_REFILL_OVER 0x0400/10 Exceed refill limit
STATUS_REFILL 0x0800/11 Refill process active
STATUS_BATCH_COMPLETE 0x1000/12 Batch process completed
ERROREEPROMWRITE 0x4000/14 EEPROM Hardware Error
STATUSCHANENABLED 0x8000/15 Set if channel is enabled
States (Word 12 of input table)
Mode (state) Table
Mode
Value Mode Value
IDLE_MODE 0 RATE_CAL_MODE 7
AUTO_MODE 1 REFILL_MODE 8
MANUAL_MODE 2 FULL_MODE 9
START_MODE 3 MANUAL_HOLD_MODE 10
STOP_MODE 4 RATECAL_HOLD_MODE 11
SHUT_OFFMODE 5 INITIAL_REFILL_MODE 12
PAUSE_MODE 6
Integrated Technician
If there is NO IT JBOX, the instrument can still measure the sense voltage, the overall
load cell millivolts per volt, and the internal reference weight value. If the user has an IT
●
●
●