HI 1769-WS/HI 1769-2WS WEIGH SCALE MODULE
4-4
Step 3. Click on the “Read IO Config” button.
(See Fig. 4-4) The “Read IO Configuration
from Online Processor” dialog box
appears. (See Fig. 4-5)
Step 4. RSLogix 500 automatically reads the I/O
information and enters them into the con
-
figuration text fields. (See Fig. 4-4)
FIG. 4-4 READ I/O CONFIGURATION FROM
ONLINE PROCESSOR DIALOG BOX
Step 5. The HI 1769-WS I/O is configured and
ready to communicate with the
MicroLogix 1500 Processor.
Step 6. For Firmware REV B you need to double
click on the module which opens the Con
-
nection Parameters dialog box. Change the
Extra Data Length from a 0 to 48. (See
Fig. 4-5)