Manual
HI 1769-WS/HI 1769-2WS WEIGH SCALE MODULE
4-12
Configuration
Parameters for the
HI 1769-WS Module
The HI 1769-WS & HI 1769-2WS are equipped with
Firmware REV B have 48 words of configuration
data. The HI 1769-WS Firmware REV B has 48
words of configuration data for CompactLogix and
Extended Data on MicroLogix, 24 words per channel.
NumAverages 16 bit integer, 1-255 20
ZeroTrackEnable 16 bit integer
0 turns auto-zero tracking off
1 turns auto-zero tracking on
0
AutoZeroTolerance 32 bit weight value, format
determined by value of
Metric Parameter
10.0 lbs.
ZeroTolerance 32 bit weight value, format
determined by value of
Metric Parameter
10.0 lbs.
Motion Tolerance 32 bit weight value, format
determined by value of
Metric Parameter
5 lbs
tareweight 32 bit weight value, format
determined by value of
Metric Parameter.
0 lbs.
SpanWeight 32 bit weight value, format
determined by value of
Metric Parameter.
Span Weight is the test weight
used at the high step of a hard
calibration
10,000.0 lbs
ROCtimebase 16 bit integer, 1-1800 seconds 10 secs
CalLowWeight 32 bit weight value, format
determined by value of
Metric Parameter
CalLowWeight is the test
weight used at the low step of
a hard calibration and as Ref
Point for C2 Calibration
0 lbs
Name Description Default
TABLE 4-1: PARAMETERS