User Manual

HI-3010 Filler/Dispenser/IBC 114
Service Manual
S - Forcing Outputs
Enter
Diagnostics
STABILITY
TEST
Activate the
test and
review the
results.
These are Opto
isolated solid-state
relays, switching 110-
240 VAC. They will
not work as a dry
contact closure
Contact Hardy
Technical
Support
Verify voltage is
being provided. The
controller will not
supply the switching
voltage
S
No
WARNING: Forcing the output relay may cause
damage or personal injury. Make absolutely sure
you know what the relay is connected to before
activating. If you are unsure, do a physical check
to determine what the selected relay is connecte
d
to BEFORE activating
Yes
PASSPASS
Use an AC meter to
physically verify
operation
The relay will
activate. Therefore
activating any
machinery attached.
Repeat for
each output
The Force Output function individually
activates each of the 4 Output relays in the
instrument. Useful in pre-startup to determine
that all the relays are connected to the correct
auxiliary devices