Installation & Operating Manual P61-2 Pellet Stove Owners Manual Safety Testing by ASTM E1509 Mobile Home Approved ìCe manuel est disponible en FranÁais sur demandeî R5 SAFETY NOTICE PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW ROOM HEATER. FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH. FOR USE IN THE U.S. AND CANADA. SUITABLE FOR INSTALLATION IN MOBILE HOMES IF THIS HARMAN STOVE IS NOT PROPERLY INSTALLED, A HOUSEFIRE MAY RESULT.
Fig.
Table of Contents Testing Label 2 Assembly & Installation 4 Venting 7 Operation 12 ESP Control 14 Maintenance 15 Trouble Shooting 18 Feeder Parts 19 Specifications 19 Wiring Diagram 20 Options 22 Parts List 23 Warranty 24 Please read this entire manual before you install and use your new room heater. Failure to follow instructions may result in property damage, bodily injury, or even death. SUITABLE FOR MOBILE HOME INSTALLATIONS.
Assembly and Installation Unpacking The P61 is bolted to the skid to prevent movement during shipping. To free the stove from the skid you must remove the hold-down bolts in the rear of the pedestal base. Removing or Installing rear cover panels To remove the rear cover panels, loosen the screws slightly and slide the covers outward as shown in the illustration. To reinstall, simply slide back into place and retighten the screws. Firebrick Install the firebrick vertically on the angle above the burnpot.
Installation Installing 9"-13" FL O O R PR O TE CT 9"-13" O 9" With Side Shields 13" Without Side Shields Fig. 3 Mobile home installation should be done in accordance with the Manufactured Home and Safety Standard (HUD), CFR 3280, Part 24. 5 6" 6" 10" FLOOR PROTECTOR With Side Shields 2" 1" Mobile Home Installation When installing this unit in a mobile home several requirements must be followed: 1. The unit must be bolted to the floor.
Venting Requirements for Terminating the Venting WARNING: Venting terminals must not be recessed into a wall or siding. NOTE: Only PL vent pipe wall pass-throughs and fire stops should be used when venting through combustible materials. NOTE: Always take into consideration the effect the prevailing wind direction or other wind currents will cause with flyash and /or smoke when placing the termination. In addition, the following must be observed: A. The clearance above grade must be a minimum of 18".1 B.
Venting A combustion blower is used to extract the combustion gases from the firebox. This causes a negative pressure in the firebox and a positive pressure in the venting system as shown in fig. 6. The longer the vent pipe and more elbows used in the system, the greater the flow resistance. Because of these facts we recommend using as few elbows as possible and 15 feet or less of vent pipe. The maximum horizontal run should not exceed 48".
Venting Venting #1 Preferred method This method provides excellent venting for normal operation and allows the stove to be installed closest to the wall. Two inches from the wall is safe; however, four inches allows better access to remove the rear panel. The vertical portion of the vent should be three to five feet high. This vertical section will provide natural draft in the event of a power failure. Fig. 8 3 ft.
Venting Venting #4 Installing into an existing chimney ( US only ) This method provides excellent venting for normal operation. This method also provides natural draft in the event of a power failure. If the chimney condition is questionable you may want to install a liner as in method #7. Fig. 10 #5 Installing into an existing fireplace chimney ( US only ) This method provides excellent venting for normal operation. This method also provides natural draft in the event of a power failure.
Venting Venting #6 Installing into an existing fireplace chimney ( US and Canada ) This method provides excellent venting for normal operation. This method also provides natural draft in the event of a power failure. In Canada and some places in the US it is required that the vent pipe extend all the way to the top of the chimney. In this method a cap should also be installed on the chimney to keep out rain. Be sure to use approved pellet vent pipe fittings.
Venting Storm collar 12" min. Flashing 3" min. 3" min. PL vent manufacturer's firestop spacer and support No insulation or other combustible materials are allowed within 3" of the PL vent pipe. Minimum flue vent configuration It is recommended that outside air be installed with this venting configuration. 18" (See Page 9 for c o r n e r installation clearances) Fig. 14 #8 Installing through the ceiling vent Fig.
P61-2 MANUAL START UP Operation Starting First Fire Be sure the power cord is plugged into a 120 volt receptacle. This can be verified by the red power light on the control panel. Fill the hopper with pellets. Fill the burn pot with pellets to a level just short of overflowing, fig. 17. Adjust feed rate. If this is your first fire or you are trying different pellets, set the feed adjuster to "3", fig. 18. This is a conservative number and will probably need to be increased.
P61-2 MANUAL IGNITION/OPERATION When to use "Stove Temp Mode" In "Stove Temp Mode" the Stove Temp Dial determines the temperature of the stove. Heat output and fuel consumption will remain constant. This makes it possible to tell how long a hopper full of pellets will last. The distribution blower speed will vary according to the position of the mode selector, fig. 21. Fig. 21 When to use "Room Temp Mode" In "Room Temp Mode" heat output is controlled automatically by the Room Sensing Probe.
ESP CONTROL P61-2 ESP CONTROL Feed adjuster Sets the maximum feed rate Power Light Indicates power to the control. Test Runs all motors at full speed for two minutes to check operation. After two minutes the stove will go to minimum burn and the blowers will alternate from high to low every two minutes to remind you that you are still in "Test Mode". Status Light Will be lit in either stove or room temp mode when pointer is not within off position band except after normal shut down.
Room Sensor and Rear Shield Installation Rear Shields Room Sensor Installation 5/16" Hex Head Screws (2 on each side) Fig. 22 5/16" Hex Head Screws (2 on each side) Fig. 23 The room sensor is a small temperature sensor on the end of a 60" gray wire. This sensor is installed much like a standard wall thermostat. Because it is so small, it can be hidden along the trim of a doorway or even up the leg of a coffee table.
Maintenance Removing Ashes: When approximatly 1 ton of pellets has been burned it will be necessary to empty the ash pan. Ashes should be placed in a metal container with a tight fitting lid. The closed container of ashes should be placed on a noncombustible floor or on the ground, well away from all combustible materials, pending final disposal.
Maintenance 7. Open burn pot slide as shown, clean with vacuum and close. 8. Clean heat exchanger with scraper as shown at left. 9. Brush or scrape the inside of the stove to remove fly ash. Fig. 26 Latch "closed "with blower cover in place. Burn pot clean-out is closed. 10. Scrape burnpot with flat end of scraper provided with the stove. Fig.31. Fig. 27 Latch "open "with blower cover partly removed. Burn pot clean-out is open. 11.Slide ash pan into stove and latch into place. Brush not supplied.
Trouble-Shooting FEEDER DOES NOT FEED 1. No pellets in hopper. 2. Feed motor will not run until ESP senses 165 deg. F. Maybe you did not put enough pellets in the burn pot before lighting the fire. 3. Feed motor has failed. 4. Something is restricting flow in the hopper or causing the slide plate to stick. 5. Firebox draft may be too low for low draft pressure switch in feeder circuit to operate. Check for closed doors, loose or missing gasket on doors or hopper lid, faulty pressure switch.
P61-2 Feeder and Specifications Specifications 32.375" 34.5" 12.375" 23.5" 9" Weight Blower Feed Rate Hopper Capacity Fuel Flue Size Outside Air Size Fuse Rating 249 lbs. 135 cfm .75 to 7.5 lbs. per hr. 72 lbs. Wood Pellets 3 inch 2 3/8 I.D. inch 5 amp 19 29.5" 5.
P61-2 Wiring Diagram 20
Door Options Optional Trim Decorative Tile To install, lay the frame face down on a soft surface. Fasten door frame by inserting the 4 threaded posts on the frame through the door. The posts should line up with the 4 holes located at the corners of the door. Once the posts are through the door, fasten frame with 4 nuts and tighten until the frame is snug. To install ash lip trim, simply slide the trim over the ash lip and into the groove on the trim. Decorative tile is available in several designs.
OPTIONS Hopper Extension Side Heat Shields Side heat shields are available to reduce the clearance to combustible materials. 22 The hopper extension allows you to put more pellet fuel in the hopper and extends burn time on one load of pellets. The hopper extension adds 60 pounds to the existing 72 pound hopper capacity, allowing you to load 132 pounds of pellets at one time.
P61 Parts List Description Part Number Hopper Gasket(6 ft.
Harman Gold Warranty HARMAN GOLD WARRANTY 6 YEAR TRANSFERABLE LIMITED WARRANTY (Residential) 1 YEAR LIMITED WARRANTY (Commercial) Harman Stove Company warrants its products to be free from defects in material or workmanship, in normal use and service, for a period of 6 years from the date of sales invoice and for mechanical and electrical failures, in normal use and service, for a period of 3 years from the date of sales invoice.