Owner's manual

HMX
CONTROL
FIRE PHONE CONTROL
Alarm
Fault
Power
Paging Microphone
Message Display
System Reset
Fault Silence
Paging All-Call
Lamp Test
Function
Switches & LEDs
Fire Phone
Handset
Master Panel
Controls and Displays
PAGING/ZONE CONTROL
MP 64/P panel
P/N HS-5010 REV. C
page 6 of 12
120 VAC
TB1 TB2
TB3 TB4 TB5P1
P2
P3
P4
J1
1
2
3
LED3LED2LED1
DCC
SSC
P3
LED1
P2
P1
MFP
Master Panel Wiring
NetCom Bus
FACP
EOLR
FACP
SIGNAL CKT
FACP
I/O Control
(Supervised)
(Non-Supervised)
H NG
(Supervised)
24V Battery
(Supervised)
+
-
(Supervised)
*1
*1
All wiring with exception of
120 VAC and Battery Connection
is Power-Limited.
Route AC power and Battery
wires to bottom-left or lower-left
side Knock-out ..
*2
*1
All Power Limited wiring must
maintain a min. 1/4“ separation
from Non Power Limited wiring.
(This requirement may be waived if
Type FPL, FPLR or FPLP wire is used
for Power Limited circuits)
*2
Wiring from FACP must be run
in conduit. Panels must be within
20’ and in the same room.
*A *A
*A - Optional wiring for
Style 7 supervision
ASC
TB1
P4
P3
P1
P2
P5
P5
Input
Card
MX-II
TB1 TB2
PWR
refer to illustration
on page 8 for info
on jumper J1 placement
1
1
2
2
3
3
AC Power
Input
Transformer
to cabinet
backplate
2519 Fourth Avenue
Moline, IL 61265
(800) 577-5758 (v)
(309) 762-8215 (f)
www.harringtonfire.com