3.4.3 Connect Cabling for the Power Source
1. Run two DC power cables (#6 insulated red connected to -48 volts) and ground (DC
return insulated black) from the site's -48VDC Distribution Panel (see Figure 3-17: -
48 Volt Breaker Distribution Panel of the DC Power Supply - Red Wire
5
and Figure
3-18: DC Return Distribution Bar - Black Wires) to each rack, attaching the cables
to the racks.
Figure 3-16: DC Power Connection Found in Each Rack - Black (DC Return) and Red (-48 Volt) wires
Figure 3-17: -48 Volt Breaker Distribution Panel of the DC Power Supply - Red Wire
5
The DC supply may not be the make shown here.
Red
–48VDC
Black
Return