User Manual

MM102225V1, Rev. B
29
Figure 3-18: DC Return Distribution Bar - Black Wires
2. If not already labeled, label OpenSky circuits in the breaker panel to identify each
rack (see Figure 3-19: Properly Labeled OpenSky Circuit Breakers in the
Distribution Panel - OpenSky Rack 1, OpenSky Rack 2, etc.)
Figure 3-19: Properly Labeled OpenSky Circuit Breakers in the Distribution Panel
3. Route cables as specified by the installation procedure, using existing cable trays and
overhead ladders, routing cables under raised floors, and so on.
4. Route DC power cables together and maintain at least two inches (2") spacing
between the DC power cable bundle and other types of cables.