Install Instructions

9
Hart & Cooley, Inc.
Installation Instructions Model TLC All-Fuel Chimney - 5" to 8"
METHOD A
6. Install an appropriate Insulated chimney length such
as a one foot (or longer if required, not to exceed 24
inches) to the horizontal branch of the insulated tee.
Lock securely into the tee branch by twisting
clockwise. A locking band must then be installed to
secure the connection. Make sure the nut and bolt
are facing down to prevent any water from collecting
in the locking band. The tee branch extension must
protrude a minimum of 3" into the room.
7. From outside the building, slide the assembly
(chimney length installed on the tee branch) through
the wall thimble, ensuring the male coupling on the
tee is facing upward. The wall thimble will provide
support until you are ready to install the wall support
assembly.
8. Place the assembled wall support against the wall
(support plate flange up) directly below the insulated
tee. Slide the wall support up to the bottom of the
insulated tee, ensuring that the flange on the top of
the support plate is inserted into the female coupler.
9. Prior to securing, ensure that the insulated tee
assembly is plumb and level and sitting flush on the
support plate. Secure to the wall through the
prepunched holes located on each side of the wall
support brackets, using (8) #14 x 1½" hex head lag
screws or #10 x 2" wood screws. Make sure they go
into solid bracing as per requirements in Table 4 Section
B and Figure 12(B), below the prepared wall thimble
opening. You can drill
5
/
32
" pilot holes. For concrete
block or poured foundation, use suitable fasteners.
10. Position the support plate to the desired distance from
the wall, as per the limits shown in Table 3 and Figure
10. Tighten the 4 nuts onto the threaded studs.
Proceed to Step 14.
METHOD B
11. Ensure that the wall support is level and secure to the
wall through the prepunched holes located on the
sides of each of the support brackets, using (8)
#14 x 1½" hex head lag screws or #10 x 1½" wood
screws. You can drill
5
/
32
" pilot holes for the lag
screws. Make sure they go into solid bracing as per
requirements. below the prepared wall thimble
opening, See Table 4 Section B and Figure 12 (B). For
concrete block or poured foundation, use suitable fasteners.
12. Place the insulated tee on the support plate, ensuring
that the male coupler of the tee is facing up and the
flange on the top of the support plate slides into the
female coupler. See Figures 15 and 16.
13. From inside the
building, for an
extension of the
insulated tee, slide
an appropriate
insulated chimney
length through the
wall thimble to the
horizontal branch of
the insulated tee.
Lock securely by
twisting clockwise.
A locking band
must then be
installed to secure
the connection.
Make sure the nut
and bolt are facing
down to prevent
any water from
collecting in the locking band. The tee branch must
protrude a minimum of 3" into the room. Use a longer
length if this is not met (not to exceed 24 inches).
THE CHIMNEY MUST EXTEND AT LEAST
3 INCHES THROUGH THE WALL INTO THE LIVING
SPACE WHERE THE STOVEPIPE CONNECTOR WILL
BE ATTACHED TO THE CHIMNEY BRANCH.