Install Instructions

Model TLC - Insulated Tee, Wall Support, Insulated Elbow Installation Instructions
INTERIOR RESUPPORT
The interior resupport is comprised of a support band with
attached straps. The interior resupport part may be used for
all sizes of chimney.
The Model TLC interior resupport allows for two different
methods of chimney resupport.
The first method is used when an immediate section of
chimney above the upper offset passes through a joist area.
With the appropriate firestop/joist shield in place, clamp the
interior resupport support band around the chimney, using two
¼” x ½” long carriage bolts and two ½” x 2” long carriage bolts
and hex nuts. Attach support band to the pipe with six sheet
metal screws as shown in Figure 6.
The interior resupport straps are then nailed to the framing
joists with at least two 8 penny nails per strap. The maximum
length of chimney that may be supported is 18 feet, which
includes the offset lengths below, any vertical run to the
resupport, and the vertical run above the interior resupport.
It does not include the length below the lower elbow/offset,
which is supported from below (Figure 6).
The second means of support is used primarily when the
immediate sections of the upper offset do not pass through a
joist area and resupport is necessary. The band is clamped
around the chimney, using two ¼” x ½” long carriage bolts
and two ¼” x 2” long carriage bolts and hex nuts. Install
band immediately below a locking band, and the straps are
nailed to the framing with at least two 8 penny nails per strap
(see Figure 7). Observe the 2” airspace minimum clearance
between the chimney and framing. The same 18-foot limit of
supportable chimney length applies to this resupport method.
©2013 Hart & Cooley, Inc. All rights reserved Form No. 851361 06/24/2013 Printed in U.S.A.
3
hartandcooley.com
(800) 433-6341