User Manual
Table Of Contents
8/16   Model 7260B-7270B/7260BT-7270BT  Page 2 of 4   
LOCATION OF UNIT: The Model 7260B-7270B/7260BT-7270BT Eyewash units 
should be installed in close proximity to potential accident areas. It should be clearly 
identified, free from obstructions and easy to access. 
SUPPLY LINE: The minimum recommended line size is 1/2” IPS with 30-90 psi (2-6 
ATM) flowing pressure. Where sediment or mineral content is a problem, an inlet 
filter is recommended. 
PLUMBING CONNECTIONS: For Model 7260B-7270B/7260BT-7270BT, the inlet 
supply is female 1/2” NPT. For Model 7260B-7270B, the waste outlet is 1-1/4” NPT. 
For Model 7260BT-7270BT, the waste outlet is 1-1/2” NPT. 
TROUBLESHOOTING 
PROBLEM 
REPAIR CHECKLIST 
1.  No flow.  1.    Check the main shut-off valve. 
2.  Insufficient water flow.  2.  a.  Verify minimum 30psi flowing supply 
line pressure. 
      b.  Probable clogging of flow control due 
to inadequate line flushing. Unscrew 
eye/face wash head and remove the 
four screws to disassemble the head. 
Clean flow control and reassemble 
head. See SP65 Installation Drawing 
for details. 
      c.  Remove cap located on L – Strainer 
using a 3/8” allen wrench to access 
and clean filter screen. 
3.  Eyewash or face wash streams 
do not meet desired eye level or 
are not balanced. 
3.    Possible blocked flow control, see 
above solution. Possible non-leveled 
eyewash assembly. 
4.  Water does not drain properly.  4.    Check the main waste line of your 
building to see if it does handle the 
capacity required for the entire 
drainage system. 
For more information about Haws products, see our website: www.hawsco.com 