User Manual

12/09 Model 7460 Page 2 of 4
LOCATION OF UNIT: The Model 7460 Eyewash should be installed in close proximity
to potential accident areas. It should be clearly identified free from obstructions and
easy to access.
SUPPLY LINE: The minimum recommended line size is 1/2” IPS with 30-90 PSI (2-6
ATM) flowing supply line pressure. Where sediment or mineral content is a problem,
an inlet filter is recommended.
PLUMBING CONNECTIONS: Inlet supply is female 1/2” IPS. Waste outlet is 1-1/4”
IPS.
TROUBLESHOOTING
PROBLEM
REPAIR CHECKLIST
1. No flow. 1.
Check the main shut-off valve.
2. Insufficient water flow. 2. a. Verify minimum 30psi flowing supply
line pressure.
b. Probable clogging of flow control
due to inadequate line flushing.
Unscrew eye/face wash head and
remove the four screws to
disassemble the head. Clean flow
control and reassemble head. See
SP65 Installation Drawing for
details.
c. Remove cap located on L – Strainer
using a 3/8” allen wrench to access
and clean filter screen.
3. Eyewash or face wash stream do
not meet desired eye level or are
not balanced.
3. Possible blocked flow control.
Possible non-leveled eyewash
assembly.
4. Water does not drain properly. 4. Check the main waste line of your
building to see if it does handle the
capacity required for the entire
drainage system.
For more information about Haws products, see our website: www.hawsco.com