15
0002080045.D
PORTABLE EYEWASH
7501/7501T/7501TH/7501T240/7501T240H
1:1
12
FV
09/21/16
5086
VWC
7 of 8
INSTALLATION
5139
2016
CC
ACTIVE
* 21-1/2"
[546mm]
33" TO 53"
[838mm TO 1346mm]
TO FINISHED FLOOR
* 22"
[559mm]
* 22"
[559mm]
* 8"
[203mm]
* 16-3/4"
[425mm]
* 10-1/8"
[257mm]
3X
ø 5/16"
ø [8mm]
MOUNTING
BRACKET
(SUPPLIED)
54-1/2" TO 66-1/2"
[1384mm TO 1689mm]
"ON"
POSITIONPOSITION
STAND BY
"OFF"
3X 1/4" MOUNTING
HARDWARE
(NOT SUPPLIED)
* 14-1/2"
[368mm]
TO FINISHED FLOOR
1 1/8"
[29mm]
2 1/4"
[57mm]
1 1/4"
[32mm]
DO NOT EXCEED WATER FILL
LINE.REFER TO INSTALLATION
INSTRUCTIONS IN "OPERATION AND
MAINTENANCE MANUAL" FOR
PROPER FILLING PROCEDURES.
NOTES:
1. TO COMPLY WITH ANSI Z358.1-2014 FOR EMERGENCY EYEWASH OR EYE/FACE WASH AND
SHOWER EQUIPMENT:
- UNIT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND
ACCEPTABLE PLUMBING PRACTICES.
- EYEWASH OR EYE/FACE WASH SHALL BE POSITIONED WITH NOZZLES NOT LESS THEN
83.8 CM (33 IN.) AND NO GREATER THAN 134.6 CM (53 IN.) FROM SURFACE ON WHICH USER
STANDS AND 15.3 CM (6 IN.) MINIMUM FROM WALL OR NEAREST OBSTRUCTION.
2. UNIT MUST BE LEVEL FROM FRONT TO BACK AND SIDE TO SIDE.
ALL THREE MOUNTING HOLES ON MOUNTING-BRACKET MUST BE USED TO PROPERLY
SECURE EYEWASH UNIT TO WALL.
(NOTES CONTINUED ON SHEET 2 OF 2)
3
3
3
MODEL 7501 (SHOWN)
MODELS 7501T/7501TH/7501T240/7501T240H - WITH
(SEE SHEET 2 OF 2)
FLOOR
LINE