Installation Guide

30°
SCALE 10:1
TOP VIEW
NOTES:
1. DIMENSIONS MAY VARY BY ± 1/2 INCH [13mm].
2. TO COMPLY WITH ANSI Z358.1-2009 FOR EMERGENCY EYEWASH OR EYE/FACE WASH AND SHOWER EQUIPMENT:
- UNIT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ACCEPTABLE PLUMBING PRACTICES.
- EYEWASH OR EYE/FACE WASH SHALL BE POSITIONED WITH NOZZLES NOT LESS THEN 83.8 CM (33 IN.) AND NO GREATER THAN
114.3 CM (45 IN.) FROM SURFACE ON WHICH USER STANDS AND 15.3 CM (6 IN.) MINIMUM FROM WALL OR NEAREST OBSTRUCTION.
- SHOWER SHALL BE POSITIONED SO THAT SHOWER HEAD IS NOT LESS THAN 208.3 CM (82 IN.) NOR MORE THAN 243.8 CM (96 IN.)
FROM SURFACE ON WHICH USER STANDS.
- SHOWER SPRAY PATTERN SHALL HAVE A MINIMUM DIAMETER OF 50.8 CM (20 IN.) AT 152.4 CM (60 IN.) ABOVE SURFACE ON WHICH
USER STANDS, AND CENTER OF SPRAY PATTERN SHALL BE LOCATED AT LEAST 40.6 CM (16 IN.) FROM ANY OBSTRUCTION.
3. DO NOT USE REGULAR PIPE SEALANT. IF NECESSARY USE DOW CORNING 832 SEALANT PLACING 5 SMALL
BEADS ON THE MALE THREADS, JUST ABOVE THE FIRST THREAD.
41
1
2
"
1056mm
6
1
2
"
167mm
61
3
4
"
1567mm
(27
1
2
")
(699mm)
89
1
4
"
2266mm
WASTE
1-1/4"
IPS
FLOOR LINE
SUPPLY
1-1/4"
IPS
L-STRAINER
3
11"
280mm
65
3
8
"
1661mm
25"
635mm
82"
2083mm
MINIMUM
SP829
3X ø
3/8"
9.5mm
B.C.
8"
203mm
ø
ø
9"
229mm
9
3
8
"
238mm
APPROVED:
DRAWN:
PART NUMBER
DRAWING NO.
SCALE:
SHEET OF
REV
DRAWING TYPE: SIZE: A
BY:ECN NO.
DATE:
DATE:
ECN:
REVISED PER
CHK'D.:
Haws Corporation - All Rights Reserved.
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
C
R
MODEL(S)
1455 KLEPPE LANE
SPARKS, NEVADA 89431
(775) 359-4712 FAX (755) 359-7424
E-MAIL: HAWS@HAWSCO.COM
WEBSITE: WWW.HAWSCO.COM
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
SLS
04/25/08
09459A00 23
0002080162.D
8300-8309/8300CRP-8309CRP
1:1
11
FV
01/08/15
VWC
INSTALLATION
4938
2014

Summary of content (1 pages)