Specification Sheet

model 92 01E
AXION
®
Thermostatic Mixing Valves
FEATURES & BENEFITS
SPECIFICATIONS
BYPASS
Best-in-class cold water bypass ow (65% of rated
tempered water ow) means continued protection under
adverse conditions.
POSITIVE SHUT OFF
Actively suspends hot water ow when cold water supply
is lost to protect against scalding.
PRESSURE DROP
Lowest internal pressure drop for this valve class –
essential where supply pressure is low.
TEMPERATURE MANAGEMENT
Parafn-based thermal actuation technology keeps outlet
temperature within tight specications to prevent scalding
and hypothermia.
SHUTTLE DESIGN
Superior shuttle design combined with premium
material selection eliminates valve binding and reduces
maintenance costs.
MIXING CHAMBER
Innovative funnel design generates turbulent ow to
ensure consistent temperature blending across entire ow
range.
DEPOSITS RESISTANT
Lime and calcium resistant materials used throughout
prevent valve sticking and provide a long service life.
FLOW RATES
Flow range of 1 to 31 GPM (117.3 L) provides service
for one emergency combination shower or multiple
eyewashes, reducing complexity and hardware costs.
MEDICALLY SUPERIOR RESPONSE
AXION’s superior design and technology provide a complete
safety solution for increased victim comfort.
EXTENDED WARRANTY
3-year extended warranty based on superior engineering
and best-in-class material selection means reliable
protection you can trust for the long term.
FLOW CAPACITIES
MODEL
9201E
INLET
1-1/4”
20
76
1
4
5
.345
13
48
10
.689
18
68
15
1
22
83
20
1.38
25
96
30
2.07
31
117
45
3.10
38
144
60
4.13
44
166
PSI
BAR
GPM
L/MIN
1-1/4”
OUTLET
MINIMUM
FLOW
PRESSURE DROP
INTERNAL COLD
WATER BY-PASS
AT 30PSI DROP
1455 Kleppe Lane :: Sparks, NV 89431 :: p. 775.359.4712 ::
f. 775.359.7424 :: e. info@hawsco.com :: www.hawsco.com :: 10 May, 2021
DISCLAIMER: Continued product improvements make specications subject to change without notice. Check www.hawsco.com for the latest product information and updates.
Model 9201E - Thermostatic Mixing Valve (patent pending)
MINIMUM MAXIMUM
Flow Rate 31 GPM 117 LPM 1 GPM 4 LPM
Hot Inlet Temperature 180° F 82° C 120° F 49° C
Recommended Hot
Inlet Temperature 140° F 60° C
Cold Inlet Temperature 70° F 21° C 40° F 4° C
Adjustable Outlet
Temperature Range 90° F 32° C 60° F 16° C
Operating Pressure 125 PSI 8.6 BAR
Factory Temperature
Set Point 85° F 29° C
Cold Water Bypass 20 GPM 76 LPM @ 30 PSID
Inlet Ports: 1-1/4” NPT(f) Outlet Port: 1-1/4” NPT(F)
Maximum Inlet Pressure Differential: +/- 10%
Listings: CSA certied per ASSE 1071, ANSI Z358.1, and
applicable sections of CSA B125.3.