Specification Sheet
model 92 01E
AXION
®
Thermostatic Mixing Valves
FEATURES & BENEFITS
SPECIFICATIONS
BYPASS
Best-in-class cold water bypass ow (65% of rated
tempered water ow) means continued protection under
adverse conditions.
POSITIVE SHUT OFF
Actively suspends hot water ow when cold water supply
is lost to protect against scalding.
PRESSURE DROP
Lowest internal pressure drop for this valve class –
essential where supply pressure is low.
TEMPERATURE MANAGEMENT
Parafn-based thermal actuation technology keeps outlet
temperature within tight specications to prevent scalding
and hypothermia.
SHUTTLE DESIGN
Superior shuttle design combined with premium
material selection eliminates valve binding and reduces
maintenance costs.
MIXING CHAMBER
Innovative funnel design generates turbulent ow to
ensure consistent temperature blending across entire ow
range.
DEPOSITS RESISTANT
Lime and calcium resistant materials used throughout
prevent valve sticking and provide a long service life.
FLOW RATES
Flow range of 1 to 31 GPM (117.3 L) provides service
for one emergency combination shower or multiple
eyewashes, reducing complexity and hardware costs.
MEDICALLY SUPERIOR RESPONSE
AXION’s superior design and technology provide a complete
safety solution for increased victim comfort.
EXTENDED WARRANTY
3-year extended warranty based on superior engineering
and best-in-class material selection means reliable
protection you can trust for the long term.
FLOW CAPACITIES
MODEL
9201E
INLET
1-1/4”
20
76
1
4
5
.345
13
48
10
.689
18
68
15
1
22
83
20
1.38
25
96
30
2.07
31
117
45
3.10
38
144
60
4.13
44
166
PSI
BAR
GPM
L/MIN
1-1/4”
OUTLET
MINIMUM
FLOW
PRESSURE DROP
INTERNAL COLD
WATER BY-PASS
AT 30PSI DROP
1455 Kleppe Lane :: Sparks, NV 89431 :: p. 775.359.4712 ::
f. 775.359.7424 :: e. info@hawsco.com :: www.hawsco.com :: 10 May, 2021
DISCLAIMER: Continued product improvements make specications subject to change without notice. Check www.hawsco.com for the latest product information and updates.
Model 9201E - Thermostatic Mixing Valve (patent pending)
MINIMUM MAXIMUM
Flow Rate 31 GPM 117 LPM 1 GPM 4 LPM
Hot Inlet Temperature 180° F 82° C 120° F 49° C
Recommended Hot
Inlet Temperature 140° F 60° C
Cold Inlet Temperature 70° F 21° C 40° F 4° C
Adjustable Outlet
Temperature Range 90° F 32° C 60° F 16° C
Operating Pressure 125 PSI 8.6 BAR
Factory Temperature
Set Point 85° F 29° C
Cold Water Bypass 20 GPM 76 LPM @ 30 PSID
Inlet Ports: 1-1/4” NPT(f) Outlet Port: 1-1/4” NPT(F)
Maximum Inlet Pressure Differential: +/- 10%
Listings: CSA certied per ASSE 1071, ANSI Z358.1, and
applicable sections of CSA B125.3.