Product Brochure

SLOPE-TOP 1200
Heavy Commercial for Hot Water or Steam
Specially designed for commercial use in heavy trac areas.
Unique one-piece heavy-duty enclosure with polyurethane
powder coated nish applied after fabrication. Easy
installation – simply secure brackets to wall, run element
and snap-on enclosure.
TABLE 2 FACTORS FOR RATINGS AT FLOW OTHER THAN STANDARD AND PRESSURE DROP VALUES
See page 4 for bracket details.
Rate of Flow GPM 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 6.0
Factor 1.000 1.016 1.028 1.038 1.045 1.051 1.057 1.062 1.067 1.074
Pressure Drop
3
4"
Tube Mill in. per ft.
47 96 157 230 320 420 525 650 775 1060
Pressure Drop 1
1
4" IPS
Steel Pipe Mill in. per ft.
3 7 12 17 24 32 41 51 62 88
Pressure Drop 1
1
4"
Tube Mill in. per ft.
6 12 20 28 39 50 63 77 93 124
Note:
If the calculated water ow rate through a baseboard unit in a completely designed hot water heating system is greater than the standard ow rate
(1 GPM), the rating of that unit may be increased by multiplying the standard rating at 1 GPM by the factor shown for the calculated ow rate.
TABLE 1 HEATING CAPACITIES, BTU PER HR PER LIN. FT. 65° ENTERING AIR TEMPERATURE
Slope-top
Model
Nominal
Tube
Size
Fin
Dim.
Thick-
ness
Fin/
Ft.
Dim.
‘A’
Water
Rate
GPM
Hot Water Ratings
Average Water Temperature °F
H W 150° 160° 170° 180° 190° 200° 210° 220° 230° 240°
ST 1200-1A
3
4"
CPR
2
1
2" 3
1
4" 0.015 55 3
7
16"
4 580 680 770 870 960 1,060 1,160 1,260 1,350 1,450
1 550 640 730 820 910 1,000 1,100 1,190 1,280 1,370
Alum. Natural Finish
ST 1200-
S125A
1
1
4"
IPS
3" 3
1
4" 0.026 48 3
13
16"
4 500 580 670 760 850 940 1,030 1,110 1,200 1,290
1 470 550 630 720 800 890 970 1,050 1,140 1,220
Painted Steel, Steam BTU. 1010 Sq. Ft./Hr. 4.2
ST 1200-3A
1
1
4"
CPR
3" 3
1
4" 0.020 54 3
11
16"
4 560 670 770 880 980 1,090 1,190 1,300 1,410 1,510
1 530 630 730 830 930 1,030 1,130 1230 1,330 1,430
Alum. Natural Finish, Steam BTU. 1290 Sq. Ft./Hr. 5.4
All the above ratings are based on active length, which is 3" less than total length, and includes a 15% addition for heating eect.
Ratings: Heating capacities are listed in Table 1 for two ow rates: 1 GPM and 4 GPM. The use of ratings at 4 GPM is limited to installations where the water
ow rate through the baseboard unit is equal to or greater than 4 GPM. Where the water ow rate through the baseboard is not known, the ratings at the
standard ow rate of 1 GPM must be used.
TM