Product Brochure

HI-OUTPUT 958-4
TABLE 5 — HEATING CAPACITIES, BTU PER HR. PER LIN. FT.
65° ENTERING AIR TEMPERATURE
HI-OUTPUT 958-3
TABLE 4 — HEATING CAPACITIES, BTU PER HR. PER LIN. FT.
65° ENTERING AIR TEMPERATURE
Nom.
Tube
Size
Water
Rate
GPM
Hot Water
Average Water Temperature °F
150° 160° 170° 180° 190° 200° 210° 220° 230° 240°
1"
CPR
4 580 700 800 910 1,010 1,120 1,230 1,340 1,450 1,550
1 550 660 760 860 960 1,060 1,160 1,270 1,370 1,470
All the above ratings are based on active length, which is 3" less than total length, and
includes a 15% addition for heating eect.
Ratings: Heating capacities are listed in Table 4 for two ow rates: 1 GPM and 4 GPM. The
use of ratings at 4 GPM is limited to installations where the water ow rate through the
baseboard unit is equal to or greater than 4 GPM. Where the water ow rate through the
baseboard is not known, the ratings at the standard ow rate of 1 GPM must be used.
Nom.
Tube
Size
Water
Rate
GPM
Hot Water
Average Water Temperature °F
150° 160° 170° 180° 190° 200° 210° 220° 230° 240°
1
1
4"
CPR
4 560 660 760 870 960 1,070 1,170 1,270 1,370 1,480
1 530 620 720 820 910 1,010 1,110 1,200 1,300 1,400
Alum. Natural Finish, Steam BTUH 1240, Sq. Ft./Hr. 5.17
All the above ratings are based on active length, which is 3" less than total length, and
includes a 15% addition for heating eect.
Ratings: Heating capacities are listed in Table 5 for two ow rates: 1 GPM and 4 GPM. The
use of ratings at 4 GPM is limited to installations where the water ow rate through the
baseboard unit is equal to or greater than 4 GPM. Where the water ow rate through the
baseboard is not known, the ratings at the standard ow rate of 1 GPM must be used.
HI-OUTPUT 958-5
TABLE 6 — HEATING CAPACITIES, BTU PER HR. PER LIN. FT.
65° ENTERING AIR TEMPERATURE
Nom.
Tube
Size
Water
Rate
GPM
Hot Water
Average Water Temperature °F
150° 160° 170° 180° 190° 200° 210° 220° 230° 240°
1
1
4"
IPS Steel
4 440 520 590 670 730 800 880 950 1,030 1,040
1 420 490 560 630 690 760 830 900 970 1,100
Painted Steel, Steam BTUH 890, Sq. Ft./Hr. 3.71
All the above ratings are based on active length, which is 3" less than total length, and
includes a 15% addition for heating eect.
Ratings: Heating capacities are listed in Table 3 for two ow rates: 1 GPM and 4 GPM. The
use of ratings at 4 GPM is limited to installations where the water ow rate through the
baseboard unit is equal to or greater than 4 GPM. Where the water ow rate through the
baseboard is not known, the ratings at the standard ow rate of 1 GPM must be used.