Product Brochure

Heavy Residential / Light Commercial
for Hot Water or Steam
The perfect alternative to bulky, commercial enclosures for
demanding heat requirements. Especially suited for problem
areas of high heat loss. 18 Gauge standard front covers.
TABLE 1 HEATING CAPACITIES, BTU PER HR PER LIN. FT. 65° ENTERING AIR TEMPERATURE
Table 2 FACTORS FOR RATINGS AT FLOW OTHER THAN STANDARD AND PRESSURE DROP VALUES
SUPR-
HEAT
MODEL
Nom.
Tube
Size
Fin
Dimensions
Thick-
ness
Fin/Ft.
Dim.
‘A’
Water
Rate
GPM
Hot Water Ratings
Average Water Temperature °F
H W 150° 160° 170° 180° 190° 200° 210° 220° 230° 240°
1000–1A
3
4"
CPR
2
1
2" 3
1
4" 0.015 55 3
5
8"
4 630 740 850 950 1,050 1,150 1,260 1,360 1,470 1,570
1 600 700 800 900 990 1,090 1,190 1,290 1,390 1,490
Alum. Natural Finish
1000–2A
1"
CPR
2
3
4" 3
1
4" 0.020 54 3
5
8"
4 610 720 840 950 1,060 1,170 1,280 1,400 1,500 1,620
1 580 680 790 900 1,000 1,110 1,210 1,320 1,420 1,530
Alum. Natural Finish
1000-S125A
1
1
4"
IPS
3" 3
1
4" 0.026 48 3
7
8"
4 430 500 570 640 710 790 860 930 1,000 1,070
1 450 530 600 680 750 840 910 980 1,060 1,130
Painted Steel, Steam BTU. 1130 Sq. Ft./Hr. 4.7
1000-3A
1
1
4"
CPR
3" 3
1
4" 0.020 54 3
7
8"
4 580 690 790 900 1,000 1,110 1,220 1,310 1,420 1,520
1 550 650 750 850 950 1,050 1,150 1,240 1,340 1,440
Alum. Natural Finish, Steam BTU. 1300 Sq. Ft./Hr. 5.4
All the above ratings are based on active length, which is 3" less than total length, and includes a 15% addition for heating eect.
Ratings: Heating capacities are listed in Table 1 for two ow rates: 1 GPM and 4 GPM. The use of ratings at 4 GPM is limited to installations
where the water ow rate through the baseboard unit is equal to or greater than 4 GPM. Where the water ow rate through the base-
board is not known, the ratings at the standard ow rate of 1 GPM must be used.
Rate of Flow GPM 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 6.0
Factor 1.000 1.016 1.028 1.038 1.045 1.051 1.057 1.062 1.067 1.074
Pressure Drop
3
4" Tube
Mill in. per ft.
47 96 157 230 320 420 525 650 775 1,060
Pressure Drop 1
1
4" IPS
Steel Pipe Mill in. per ft.
3 7 12 17 24 32 41 51 62 88
Pressure Drop 1
1
4"
Tube Mill in. per ft.
6 12 20 28 39 50 63 77 93 124
Note: If the calculated water ow rate through a baseboard unit in a completely designed hot water heating system is greater than the standard ow rate
(1 GPM), the rating of that unit may be increased by multiplying the standard rating at 1 GPM by the factor shown for the calculated ow rate.
SUPR-HEAT 1000