Installation Guide
TriStar
™
Pump Series ____________________ ____________________________Page 7 of 15
Electrical (cont’d.)
Wiring
WARNING – All electrical wiring MUST be in conformance with all applicable local codes, regulations,
and the National Electric Code (NEC).
Pump MUST be permanently connected to circuit. If other lights or appliances are also on the same circuit, be sure
to add their amp loads before calculating wire and circuit breaker sizes. Use the load circuit breaker as the Master
On-Off switch.
Motor Specifications
Motor Brake Horsepower Motor Rated Horsepower Motor Electric V/A Wire Size / Breaker
HP (kW) HP (kW) Voltage Amps AWG Amps
0.99 (0.74) 0.50 (0.37) 208 - 230 / 115 5.3 - 4.9 / 9.8 14 10 / 15
1.39 (1.04) 0.75 (0.56) 208 - 230 / 115 7.0 - 6.2 / 12.4 14 10 / 15
1.85 (1.38) 1.00 (0.75) 208 - 230 / 115 8.5 - 7.4 / 14.8 14 / 12 15 / 20
2.40 (1.79) 1.50 (1.12) 208 - 230 / 115 11.2 - 10.2 / 20.4 14 / 10 15 / 30
2.70 (2.01) 2.00 (1.49) 208 - 230 11.8 - 11.0 14 15
2.70 (2.01) ** 2.00 (1.49) ** 208 - 230 ** 7.0 - 6.6 ** 14 ** 10 **
3.60 (2.69) 3.00 (2.24) 208 - 230 16.0 - 14.8 12 20
3.60 (2.69) * 3.00 (2.24) * 208 - 230 / 460 * 9.6 - 9.4 / 4.7 * 14 * 15 / 10 *
5.00 (3.73) 5.00 (3.73) 208 - 230 21.0 - 19.4 10 30
1.85 / 0.22 (1.38 / 0.16) 1.00 / 0.12 (0.75 / 0.09) 208 - 230 8.6 - 8.2 ¹ 14 15
2.40 / 0.28 (1.79 / 0.21) 1.50 / 0.18 (1.12 / 0.13) 208 - 230 11.4 - 10.4 ² 14 15
Full Rate Pumps
2.70 / 0.33 (2.01 / 0.25) 2.00 / 0.25 (1.49 / 0.19) 208 - 230 12.4 - 11.2 ³ 14 15
0.94 (0.70) 0.75 (0.56) 230 / 115 5.4 / 10.8 14 10 / 15
1.25 (0.93) 1.00 (0.75) 230 / 115 7.0 / 14.0 14 / 12 10 / 20
1.65 (1.23) 1.50 (1.12) 230 / 115 7.7 / 15.4 14 / 12 10 / 20
2.20 (1.64) 2.00 (1.49) 230 / 115 10.8 / 21.6 14 / 10 15 / 30
2.60 (1.94) 2.50 (1.86) 230 11.5 14 15
3.45 (2.57) 3.00 (2.24) 230 13.5 12 20
1.85 / 0.22 (1.38 / 0.16) 1.50 / 0.18 (1.12 / 0.13) 208 - 230 8.6 - 8.2 ¹ 14 15
2.40 / 0.28 (1.79 / 0.21) 2.00 / 0.25 (1.49 / 0.19) 208 - 230 11.4 - 10.4 ² 14 15
Max Rate Pumps
2.70 / 0.33 (2.01 / 0.25) 2.50 / 0.30 (1.86 / 0.22) 208 - 230 12.4 - 11.2 ³ 14 15
0.75 (0.56) 0.75 (0.56) 220 / 110 7.0 / 14.0 14 / 12 10 / 20
1.00 (0.75) 1.00 (0.75) 220 / 110 8.0 / 16.0 14 / 12 10 / 20
1.50 (1.12) 1.50 (1.12) 220 / 110 9.8 / 19.6 14 / 10 15 / 30
2.00 (1.49) 2.00 (1.49) 220 11.0 14 15
3.00 (2.24) 3.00 (2.24) 220 12.0 14 15
50 Hz Pumps
3.00 (2.24) * 3.00 (2.24) * 380 - 415 / 190 * 4.9 - 4.8 / 9.8 * 14 * 10 / 15 *
¹
,
²
,
³ Low Speed Amps: (¹ 2.8 - 3.0) (² 3.2 - 3.4) (³ 3.8 - 4.1)
* Three-Phase (3Φ) Pump - motor starter required
** Three-Phase (3Φ) Pump - variable-speed applications only (Not available as a stand-alone pump. May only be used with SP3220VSC.)
Start-Up & Operation
Prior to Start-Up
NOTE - If it is necessary to perform a pressure test, prior to initial use to ensure pump is functioning properly, then the
following criteria should be maintained for this test:
1. Have a professional perform this test.
2. Ensure all pump and system components are sealed properly to prevent leaks.
3. Remove any trapped air in the system by fully opening filter manual air relief valve until a
steady stream of water (not air or air and water mix) is discharged from the valve.
4. Allow no more than 50 psi (345 kPa) at a water temperature no higher than 100° F (38° C).
5. Run pressure test for no longer than 24 hours. Immediately inspect all parts to verify they are
intact and functioning properly.
WWW.HAYWARDPOOL.COM USE ONLY HAYWARD GENUINE REPLACEMENT PARTS