Installation & Owner’s Manual AIR HANDLERS: Variable Speed AHGV Hydronic Air Handler HAGV Electric Air Handler with Optional Heat Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.
1 Variable Speed Air Handlers Installation & Owners Manual Table of Contents Unit Nomenclature..................................2 Control Wiring........................................5 General Information................................3 ECM Blower Motor................................5 Inspection................................................3 Hot Water Piping.....................................6 Reference................................................3 Condensate Piping....................
Installation & Owners Manual Variable Speed Air Handlers 2 Unit Nomenclatures AHGV: HAGV: Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.
3 Variable Speed Air Handlers Installation & Owners Manual Air Handler Installation Instructions Electric and Hydronic Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.
Installation & Owners Manual Variable Speed Air Handlers 4 Air Handler Installation Instructions Electric and Hydronic INSTALLATION/OPERATION SAFETY RULES: 1. Read these rules and instructions carefully. Failure to follow these rules and the installation instructions could cause a malfunction of the unit, and a possible safety hazard. Keep these instructions nearby the unit for future reference. 2.
5 Variable Speed Air Handlers Installation & Owners Manual Air Handler Installation Instructions Electric and Hydronic UPFLOW APPLICATION: In an upflow installation the discharge outlet is at the top. Care should be taken to insure unit is level to permit proper condensate drainage. Normal upflow installation will be in a closet or basement. If installed in a closet, the closet should have a platform framed in, with an opening at the top of the platform centered in the closet.
Installation & Owners Manual 6 Variable Speed Air Handlers Air Handler Installation Instructions Electric and Hydronic PIPING: HOT WATER WATERPIPING PIPING:FOR HYDRONIC AHGV UNITS: If a residential water heater is used for space heating water, do not exceed a distance of 70’ between the air handler and the water heater. The water heater should be the quick recovery type. Air handler and water heater must be located indoors and not subject to freezing temperatures.
7 Variable Speed Air Handlers Installation & Owners Manual Single Piece Air Handler Installation Instructions Electric and Hydronic CHECK TEST AND START UP: HAGV UNITS: Air handler with optional electric heat : The unit should be tested after the system has been completely installed to determine proper operation. Unit is equipped with heater time delay controls. If electric heater is field installed, all heating elements should turn on within one minute.
Installation & Owners Manual Variable Speed Air Handlers 8 ELECTRICAL DATA Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.
9 Variable Speed Air Handlers Installation & Owners Manual HYDRONIC PERFORMANCE DATA Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.
Installation & Owners Manual Variable Speed Air Handlers 10 BLOWER PERFORMANCE DATA Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.
11 Installation & Owners Manual Variable Speed Air Handlers HAGV Dimensioal Data Air Handler with Optional Electric Heat DIMENSIONS (inches)* MODELS A B C D E F G H J K L M N P R HAGV24-00-1A HAGV36-00-1A 21.00 48.00 21.00 19.00 12.50 14.50 13.00 6.75 20.00 17.00 12.75 10.30 2.30 4.35 5.00 HAGV48-00-1A HAGV60-00-1A 24.50 58.75 21.75 23.35 21.25 19.75 17.25 6.75 26.00 23.00 16.75 14.35 2.30 4.35 4.50 * All dimensions are approximate Heat Controller, Inc.
Installation & Owners Manual 12 Variable Speed Air Handlers AHGV Dimensioal Data Hydronic Air Handler DIMENSIONS (inches)* MODELS A B C D E F G H AHGV24/36 21.00 48.00 21.00 19.00 15.00 14.50 13.00 6.75 AHGV48/60 24.50 58.75 21.75 23.50 15.75 19.75 17.25 6.75 J K L M N P 2.30 26.00 23.00 16.75 14.35 2.30 20.00 17.00 13.00 10.30 R S T U 4.35 3.75 1.75 2.50 1.50 4.35 3.50 2.25 1.25 1.50 * All dimensions are approximate Heat Controller, Inc. • 1900 Wellworth Ave.
04/2009 6/2009