Quick Start Manual

24
FIGURE 18
A
LTERNATE HORIZONTAL DIRECT VENT TERMINATION
N
OT APPLICABLE TO
G
LDB75
G
LDB90
G
LDB105
Insulate the entire length of vent
pipe, between the elbow where the
pipe exits the wall and the elbow
where the termination is made, with
a
closed-cell insulation, such as
Arm-a-Flex” or “Rub-a-Tex” with a
minimum of 1/2” thickness.
All elbows installed on the exterior
of the building must be of the long
sweep nature.
As required for the horizontal piping
ran within the structure, any pipe
ran horizontal outside the structure
must slope upward a minimum of
1/4” per foot run so that condensate
drains toward the furnace.
From the top elbow in the exhaust
pipe, extend a length of PVC pipe
outward so that it terminates exactly
12 inches from the wall. See Figure
18.
The 45,000 BTUH unit only uses kit
RXGY-D02 or D02A. The 60,000
BTUH and 75,000 BTUH units may
use kits RXGY-D02 or D02A or
RXGY-D03 or D03A depending on
pipe lengths and number of elbows.
See Table 2.
The following are parts lists for the
RXGY-D02 or D02A, RXGY-D03 or
D03A alternate horizontal direct vent
termination kits:
RXGY-D02/D02A
1. 2-in. tee with reducer assembly
2.
1
2-in. PVC 6-in. dia. trap
3. PVC vane
4. 2-in. PVC elbow
5. 1
1
2-in. PVC nipple with coupling
6. PVC strap
7. vent template
RXGY-D03/D03A
1. 3-in. tee with reducer assembly
2.
1
2-in. PVC 6-in. dia. trap
3. PVC vane
4. 2-in. PVC elbow
5. PVC strap
6. vent template
S
EE DETAIL A
60”
MAX.
P
IPE
S
UPPORT
S
TRAP
3 MAX.
NOTE: 3-1/2
M
AX. WHEN
D04 KIT IS
U
SED.
E
XHAUST VENT
2
" PVC FOR MODELS WITH INPUTS OF 45,000 AND
1
05,000 BTU. ELBOWS AND RISERS ARE 2" PVC.
2
" PVC ELBOWS AND RISER
M
ODELS WITH INPUTS OF 45,000
T
HRU 105,000 BTU.
USE KIT NO. RXGY-D02 WHEN 2" PIPE
IS USED BETWEEN FURNACE AND
OUTSIDE WALL. USE KIT NO. RXGY-D03
WHEN 3" PIPE IS USED.
I339
1
2
F
R
OM
WA
L
L
3
2
4
M
IN.
EXHAUST
INTAKE
OPTIONAL
INTAKE
DETAIL B
EXHAUST / INTAKE RELATIONSHIP
RXGY-D02A
1. 2” Tee assembly w/
1
2 drain
connection
2.
1
2 PVC-5” diameter trap
3. Wind deflector vane
4. Vent template
RXGY-D03A
1. 3” Tee assembly w/
1
2 drain
connection
2.
1
2 PVC-5” diameter trap
3. Wind deflector vane
4. Vent Template
24”
MAX.