Quick Start Manual
24
FIGURE 18
A
LTERNATE HORIZONTAL DIRECT VENT TERMINATION
N
OT APPLICABLE TO
G
LDB75
G
LDB90
G
LDB105
• Insulate the entire length of vent
pipe, between the elbow where the
pipe exits the wall and the elbow
where the termination is made, with
a
closed-cell insulation, such as
“
Arm-a-Flex” or “Rub-a-Tex” with a
minimum of 1/2” thickness.
• All elbows installed on the exterior
of the building must be of the long
sweep nature.
• As required for the horizontal piping
ran within the structure, any pipe
ran horizontal outside the structure
must slope upward a minimum of
1/4” per foot run so that condensate
drains toward the furnace.
From the top elbow in the exhaust
pipe, extend a length of PVC pipe
outward so that it terminates exactly
12 inches from the wall. See Figure
18.
The 45,000 BTUH unit only uses kit
RXGY-D02 or D02A. The 60,000
BTUH and 75,000 BTUH units may
use kits RXGY-D02 or D02A or
RXGY-D03 or D03A depending on
pipe lengths and number of elbows.
See Table 2.
The following are parts lists for the
RXGY-D02 or D02A, RXGY-D03 or
D03A alternate horizontal direct vent
termination kits:
RXGY-D02/D02A
1. 2-in. tee with reducer assembly
2.
1
⁄2-in. PVC 6-in. dia. trap
3. PVC vane
4. 2-in. PVC elbow
5. 1
1
⁄2-in. PVC nipple with coupling
6. PVC strap
7. vent template
RXGY-D03/D03A
1. 3-in. tee with reducer assembly
2.
1
⁄2-in. PVC 6-in. dia. trap
3. PVC vane
4. 2-in. PVC elbow
5. PVC strap
6. vent template
S
EE DETAIL A
60”
MAX.
P
IPE
S
UPPORT
S
TRAP
3” MAX.
NOTE: 3-1/2”
M
AX. WHEN
D04 KIT IS
U
SED.
E
XHAUST VENT
2
" PVC FOR MODELS WITH INPUTS OF 45,000 AND
1
05,000 BTU. ELBOWS AND RISERS ARE 2" PVC.
2
" PVC ELBOWS AND RISER
M
ODELS WITH INPUTS OF 45,000
T
HRU 105,000 BTU.
USE KIT NO. RXGY-D02 WHEN 2" PIPE
IS USED BETWEEN FURNACE AND
OUTSIDE WALL. USE KIT NO. RXGY-D03
WHEN 3" PIPE IS USED.
I339
1
2
”
F
R
OM
WA
L
L
3”
2
4”
M
IN.
EXHAUST
INTAKE
OPTIONAL
INTAKE
DETAIL B
EXHAUST / INTAKE RELATIONSHIP
RXGY-D02A
1. 2” Tee assembly w/
1
⁄2” drain
connection
2.
1
⁄2” PVC-5” diameter trap
3. Wind deflector vane
4. Vent template
RXGY-D03A
1. 3” Tee assembly w/
1
⁄2” drain
connection
2.
1
⁄2” PVC-5” diameter trap
3. Wind deflector vane
4. Vent Template
24”
MAX.