SUBMITTAL DATA Unit Designation Water Source Heat Pump Systems Job Name Architect Engineer Contractor PERFORMANCE DATA Cooling Capacity BTUH EER Heating Capacity BTUH COP Models HBH 072 - 120 60 Hz R-410A Ambient Air oF Entering Water Temp (Cooling) oF Entering Air Temp (Cooling) oF Entering Water Temp (Heating) oF Entering Air Temp (Heating) oF Airflow Fan Speed or Motor RPM/Turns Operating Weight Minimum Circuit Ampacity Maximum Overcurrent Protection 1900 Wellworth Ave.
Engineering Design Guide Submittal Data HBH SERIES Series Heat Controller, Inc. Table of Contents Selection Procedure ................................................................................................................................................................2 HBH Series Nomenclature ......................................................................................................................................................4 Performance Data - AHRI/ASHRAE/ISO 13256-1...........
Heat Controller, Inc. EngineeringSubmittal Design Guide Data HBH SERIES Series Selection Procedure Reference Calculations Heating Cooling HE LWT = EWT GPM x 500 LAT = EAT + HR LWT = EWT + GPM x 500 HC CFM x1.08 LAT (DB) = EAT (DB) - LC = TC - SC SC CFM x1.
Submittal Data Engineering Design Guide HBH SERIES Series Heat Controller, Inc. Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions. Step 2 Obtain the following design parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 450 CFM per ton.
Heat Controller OEM Price List HBH Large Compact Horizontal Units Heat Controller, Inc. HBH SERIES Series Entering Water Temperature Range: 20 - 120° F (-6. 7 - 48.9° C) Horizontal Sizes 072 - 120 Model Nomenclature EngineeringSubmittal Design Guide Data HBH Large Model Structure 3 Basic Unit Description: • Reversing Valve - 4-way, pilot operated, solenoid activated in cooling.
Submittal Data Engineering Design Guide Heat Controller, Inc. HBH SERIES Series Performance Data AHRI/ASHRAE/ISO 13256-1 ASHRAE/AHRI/ISO 13256-1. English (I-P) Units Water Loop Heat Pump Model Cooling 86°F Capacity Btuh EER Btuh/W HBH072 69,000 HBH096 95,000 HBH120 119,000 Ground Water Heat Pump Heating 68°F Capacity Btuh COP 13.3 92,500 13.7 123,000 13.3 160,000 Cooling 59°F Capacity Btuh EER Btuh/W 5.0 78,500 5.0 104,500 4.
Heat Controller, Inc. EngineeringSubmittal Design Guide Data HBH SERIES Series Performance Data Selection Notes For operation in the shaded area when water is used in lieu of an anti-freeze solution, the LWT (Leaving Water Temperature) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 42°F [5.6°C] when the JW3 jumper is not clipped (see example below). This is due to the potential of the refrigerant temperature being as low as 32°F [0°C] with 40°F [4.
Submittal Data Engineering Design Guide Heat Controller, Inc. HBH SERIES Series Performance Data: HBH072 2400 CFM Nominal Airflow Heating & Cooling Performance capacities shown in thousands of Btuh WATER/BRINE Cooling - EAT 80/67°F EWT °F FLOW gpm PD psi PD ft. 20 20.00 6.8 15.8 10.00 1.2 2.7 82.3 56.8 3.6 94.5 15.00 3.3 7.7 81.1 55.8 3.4 20.00 6.2 14.3 80.2 55.1 10.00 1.0 2.2 82.4 15.00 3.0 7.0 20.00 5.6 10.
Heat Controller, Inc. EngineeringSubmittal Design Guide Data HBH SERIES Series Performance Data: HBH096 3200 CFM Nominal Airflow Heating & Cooling Performance capacities shown in thousands of Btuh WATER/BRINE Cooling - EAT 80/67°F EWT °F FLOW gpm PD psi PD ft. 20 24.0 10.2 23.5 12.0 2.1 4.9 109.6 77.9 4.9 126.2 18.0 5.3 12.1 109.3 77.9 4.7 24.0 9.3 21.4 108.9 77.8 12.0 1.9 4.4 108.7 18.0 4.8 11.0 24.0 8.4 12.
Submittal Data Engineering Design Guide Heat Controller, Inc. HBH SERIES Series Performance Data: HBH120 4000 CFM Nominal Airflow Heating & Cooling Performance capacities shown in thousands of Btuh WATER/BRINE Cooling - EAT 80/67°F EWT °F FLOW gpm PD psi PD ft. 20 30.00 16.0 36.9 15.00 4.0 9.2 141.5 98.1 6.6 163.9 22.50 8.6 19.9 140.4 98.2 6.3 30.00 14.5 33.4 139.2 98.0 15.00 3.5 8.0 140.6 22.50 7.7 17.8 30.00 13.0 15.
Heat Controller, Inc. EngineeringSubmittal Design Guide Data HBH SERIES Series HBH Performance Data Correction Tables Air Flow Correction Table Percentage of Rated Airflow Cooling Total Capacity Sensible Capacity Heating Power Heat of Rejection Heating Capacity Power Heat of Extraction 75% 0.957 0.869 0.951 0.955 0.970 1.054 0.964 81% 0.966 0.901 0.963 0.966 0.978 1.035 0.975 88% 0.976 0.933 0.974 0.976 0.986 1.017 0.987 94% 0.988 0.966 0.987 0.988 0.993 1.009 0.
Submittal Data Engineering Design Guide Heat Controller, Inc. HBH SERIES Series Antifreeze Correction Table Cooling Heating EWT 90°F EWT 30°F Antifreeze Type Antifreeze % Total Cap Sens Cap Power Water 0 1.000 1.000 1.000 5 0.995 0.995 Propylene Glycol 15 0.986 0.986 25 0.978 5 Methanol Ethanol Ethylene Glycol WPD Corr. Fct. EWT 30°F Htg Cap Power 1.003 0.989 0.997 1.070 1.009 0.968 0.990 1.210 0.978 1.014 0.947 0.983 1.360 0.995 0.995 1.002 0.989 0.997 1.
Heat Controller, Inc. EngineeringSubmittal Design Guide Data HBH SERIES Series Blower Performance Data HBH072 - Standard Unit All Data is Wet Coil SCFM 1800 1900 ESP 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 BHP 0.00 0.10 0.28 0.32 0.35 0.39 0.42 0.45 0.48 0.52 0.56 0.60 0.64 0.69 0.72 0.
Submittal Data Engineering Design Guide Heat Controller, Inc. HBH SERIES Series Blower Performance Data HBH096 - Standard Unit All Data is Wet Coil SCFM 2400 2500 2600 2700 2800 2900 3000 3100 3200 ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 BHP 0.45 0.50 0.54 0.59 0.63 0.69 0.74 0.80 0.85 0.90 0.94 0.99 1.04 1.10 1.16 1.
Heat Controller, Inc. EngineeringSubmittal Design Guide Data HBH SERIES Series Blower Performance Data HBH096 - Standard Unit Table Continued from Previous Page All Data is Wet Coil SCFM 3300 3400 3500 3600 3700 3800 3900 4000 ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 BHP 1.01 1.08 1.14 1.21 1.28 1.33 1.39 1.45 1.51 1.58 1.64 1.72 1.78 1.84 1.93 2.
Submittal Data Engineering Design Guide Heat Controller, Inc. HBH SERIES Series Blower Performance Data HBH120 - Standard Unit All Data is Wet Coil SCFM 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 BHP 0.75 0.81 0.86 0.91 0.97 1.03 1.09 1.15 1.21 1.27 1.34 1.41 1.47 1.54 1.61 1.
Heat Controller, Inc. EngineeringSubmittal Design Guide Data HBH SERIES Series Blower Performance Data HBH120 - Standard Unit Table Continued from Previous Page All Data is Wet Coil SCFM 4300 4400 4500 4600 4700 4800 4900 5000 ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 BHP 2.00 2.07 2.16 2.23 2.31 2.41 2.49 2.57 2.66 2.74 2.84 2.94 3.02 3.
Submittal Data Engineering Design Guide Heat Controller, Inc. HBH SERIES Series HBH Physical Data Model 072 096 Compressor Quantity Number of Circuits (Compressors) Factory Charge R-410a (oz) [kg] per circuit 120 Scroll 2 60 [1.70] 76 [2.15] 80 [2.27] Blower Motor Blower Motor Quantity 1 Standard Motor (hp) [kw] 1 [0.75] 2 [1.49] 3 [2.24] Large Motor (hp)[KW] (2)[1.49] 3[2.24] 5[3.73] Blower No. of Blowers 1 Blower Wheel Size D x W (in0 [cm] 12 x 12 [30.48 x 30.
RN STRAIGHT DISCHARGE Heat Controller, Inc. EngineeringSubmittal Design Guide Data HBH SERIES Series HBH072-120 Dimensional Data RIGHT RETURN STRAIGHT DISCHARGE LEFT RETURN STRAIGHT DISCHARGE CBP 1 5 1 B 4 2 CAP CAP CAP A 2 F FRONT LEFTORETURN SERVICE ACCESS CAP 3Õ (91 cm.
Submittal Data Engineering Design Guide Heat Controller, Inc. HBH SERIES Series HBH072-120 Dimensional Data Discharge Connections Duct Flange Overall Cabinet A B C Depth Width Height in. 36.3 84.9 21.6 cm. 92.2 215.6 54.9 Model 072-120 D Water Connections E F G Supply Depth Supply Width Supply Height 14.0 17.0 13.5 7.8 35.6 43.2 34.3 19.8 HBH072-120 Corner Weights K L M Water Outlet Water Inlet 15.0 8.3 4.0 2.0 18.8 16.8 38.1 21.1 10.2 5.1 47.8 42.
Heat Controller, Controller, Inc. Inc.
Submittal Data Engineering Design Guide HBH SERIES Series Typical Wiring Diagram Three Phase HBH072-120 With CXM Controller 21 Heat Controller, Inc.
Heat Controller, Inc. HBH Series 60Hz Engineering Specifications HBH SERIES Series EngineeringSubmittal Design Guide Data Page 1 NOTICE! This product specification document is furnished as a means to copy and paste Heat ClimateMaster Controller product information into a project specification. It is not intended to be a complete list of product requirements. This document is an excerpt from the product submittal and must not be used without consulting the complete product submittal.
Submittal Data Engineering Design Guide HBH Series 60Hz Engineering Specifications HBH SERIES Series Heat Controller, Inc. Page 2 General: Furnish and install the HBH Series as indicated on the plans. Equipment shall be completely assembled, piped and internally wired. Capacities and characteristics as listed in the schedule and the specifications that follow. Units shall be supplied completely factory built capable of operating over an entering water temperature range from 20° to 120°F (-6.7° to 48.
Heat Controller, Inc. HBH Series 60Hz Engineering Specifications HBH SERIES Series EngineeringSubmittal Design Guide Data Page 3 Fan and Motor Assembly: All units shall have belt-driven single centrifugal fan. Fan motor shall be permanently lubricated with thermal overload protection. Units supplied without permanently lubricated motors must provide external oilers for easy service. The fan and motor assembly must be capable of overcoming the external static pressures as shown on the schedule.
Submittal Data Engineering Design Guide HBH SERIES Series Heat Controller, Inc. HBH Series 60Hz Engineering Specifications Page 4 Option: The unit shall be supplied with stainless steel drain pan. Electrical: A control box shall be located within the unit compressor compartment and shall contain a 75VA transformer with load side circuit breaker protection, 24 volt activated, 2 or 3 pole compressor contactor, terminal block for thermostat wiring and solid-state controller for complete unit operation.
Heat Controller, Inc. HBH Series 60Hz Engineering Specifications HBH SERIES Series EngineeringSubmittal Design Guide Data Page 5 Hose Kit Assemblies: The following assemblies ship with the valves already assembled to the hose described: a. Supply and return hoses having ball valve with PT port. b. Supply hose having ball valve with PT port; return hose having automatic flow regulator valve with PT ports, and ball valve. c.
11/2010 04/2009 06/2012