Application, Operation, & Maintenance Manual DXM2 UNIT CONTROLS Heat Controller, Inc.
Note: The compressor will have a 5-minute anti-short
cycle delay at power-up.
Standby/Fan Only - In Standby Mode, the compressor will
be off. The selected fan output(s) and RV relay may be
on if appropriate inputs are present. If there is demand for
constant fan, the appropriate fan output(s) will be activated
for low speed operation, or constant fan air ow. If there is
demand for constant high speed fan, the appropriate fan
output(s) will be activated for high speed operation, or high
speed constant fan air ow.
Note: DIP1.5 (Dehum Fan Mode Select) has no effect
upon constant fan operation.
The RV relay will not directly track the input demands for
RV, the DXM2 Control will employ “smart RV” control.
This ensures that the RV will only switch positions if the
thermostat has called for a Heating/Cooling Mode change.
Heating Stage 1 - In Heating Stage 1 Mode, the selected
Fan output(s) and the Compressor relay are turned on
immediately. If con gured as Stage 2 (DIP1.2 = off), then
the Compressor and Fan will not turn on until there is Stage
2 demand. The Compressor relay is turned off immediately
when the Heating Stage 1 demand is removed. The
selected Fan output(s) will turn off after the selected
heating blower off delay, and the control then reverts to
Standby Mode. If there is a Master/Slave situation or a
Dual Compressor situation, all Compressor relays and
related functions will track with their associated DIP1.2.
Heating Stage 2 – In Heating Stage 2 Mode, the selected
Fan output(s) and Compressor relays remain on. The
Compressor Speed relay is turned on, and multi–stage fan
con gurations switch to the appropriate operating speed
for Heating Stage 2 immediately. The Compressor Speed
relay is turned off immediately when the Heating Stage 2
demand is removed, and multi–speed fan con gurations
switch to the appropriate operating speed for Heating
Stage 1 immediately, and the control reverts to Heating
Stage 1 Mode. If there is a Master/Slave situation or a Dual
Compressor situation, all Compressor relays and related
functions will track with their associated DIP1.2.
Heating Stage 3 – In Heating Stage 3 Mode, the selected
Fan output, Compressor, and Compressor Speed relays
will remain on. The EH1 output will turn on immediately,
and if the control is operating an ECM Blower, the air ow
DXM2 Controls
Table 3: LED and Alarm Relay Output Table