Quick Start Manual
20
HMB36VA1E
Cooling Airflow Heating Airflow
A/B Switch Setting
0=OFF,1=ON
COOL Switch Setting
0=OFF,1=ON
Airflow
(CFM)
A/B Switch Setting
0=OFF,1=ON
Heater Kit
Installed (KW)
Airflow
(CFM)
5 6 7 8
0 0 0 0 0 525 0 0 600
0 0 0 0 1 560 0 5 800
0 0 0 1 0 600 0 8 1000
0 0 0 1 1 625 0 10 1000
0 0 1 0 0 700 0 15 1300
0 0 1 0 1 750 0 20
N/A
0 0 1 1 0 800 0 25
N/A
0 0 1 1 1 850
0 30
N/A
0 1 0 0 0 875
0 1 0 0 1 890
0 1 0 1 0 930
0 1 0 1 1 950
0 1 1 0 0 1000
0 1 1 0 1 1050
0 1 1 1 0 1125
0 1 1 1 1 1200
HMB48VB1E
Cooling Airflow Heating Airflow
A/B Switch Setting
0=OFF,1=ON
COOL Switch Setting
0=OFF,1=ON
Airflow
(CFM)
A/B Switch Setting
0=OFF,1=ON
Heater Kit
Installed (KW)
Airflow
(CFM)
5 6 7 8
1 0 0 0 0 525 1 0 700
1 0 0 0 1 560 1 5 900
1 0 0 1 0 600 1 8 1100
1 0 0 1 1 650 1 10 1100
1 0 1 0 0 700 1 15 1300
1 0 1 0 1 750 1 20 1500
1 0 1 1 0 800 1 25
N/A
1 0 1 1 1 850
1 30
N/A
1 1 0 0 0 875
1 1 0 0 1 950
1 1 0 1 0 1050
1 1 0 1 1 1150
1 1 1 0 0 1250
1 1 1 0 1 1350
1 1 1 1 0 1400
1 1 1 1 1 1600
HMB60VC1E
Cooling Airflow Heating Airflow
A/B Switch Setting
(*=either0or1)
COOL Switch Setting
0=OFF,1=ON
Airflow
(CFM)
A/B Switch Setting
(*=either0or1)
Heater Kit
Installed (KW)
Airflow
(CFM)
5 6 7 8
* 0 0 0 0 1100 * 0 800
* 0 0 0 1 1200 * 5 1000
* 0 0 1 0 1250 * 8 1200
* 0 0 1 1 1300 * 10 1200
* 0 1 0 0 1350 * 15 1400
* 0 1 0 1 1400 * 20 1600
* 0 1 1 0 1450 * 25
N/A
* 0 1 1 1 1500
* 30
N/A
* 1 0 0 0 1550
NOTES:
• Airow values listed are for 240V operation. For
208V operation, multiply the CFM value by .95 for
HMB36VA1E & HMB48VB1E units. For HMB60VC1E
units, mulitply the CFM value by .90.
• Whenmatchedwithtwo-stageoutdoorunitstheairow
on low (Y1 or W1) input only will be 70% of the values
shown in this table.
* 1 0 0 1 1600
* 1 0 1 0 1650
* 1 0 1 1
1700
* 1 1 0 0 1750
* 1 1 0 1 1800
* 1 1 1 0 1900
* 1 1 1 1 2000
Table 8. Airflow Data for HMB**V*1E Series Air Handlers