Service Manual Packaged Terminal Air Conditioners & Heat Pumps 7,000-15,000 BTUH Cooling with Electric Heat EKTC07-2G EKTC07-1G EKTC09-2G EKTC09-1G EKTC12-2G EKTC12-1G EKTC15-2G EKTC15-1G Heat Pump with Electric Heat EKTH07-2G EKTH07-1G EKTH09-2G EKTH09-1G EKTH12-2G EKTH12-1G EKTH15-2G EKTH15-1G Heat Controller • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.
PACKAGED TERMINAL A/C Heat Controller Service Manual Unit nomenclature EKTC 07 - 1 G MODEL REVISION G=Green R-410A Refrigerant Gas EKTC—Cooling only with Electric Heat EKTH—Heat Pump with Electric Heat BTU/H 07K 09K 12K 15K VOLTAGE CODE 1=208/230V-60Hz 2=265V-60Hz (consult factory) Dimensional Data 42” AIR DISCHARGE GRILLE IS REVERSIBLE TO PROVIDE EITHER 40° OR 80°DISCHARGE ANGLE 22” 40” 6” 1” 24” 10” 1” 80° Location of external drain holes on bottom flange of wall sleeve 40° 8” 13.
Heat Controller Service Manual Unit components 2 Packaged Terminal A/C
PACKAGED TERMINAL A/C Heat Controller Service Manual Specification and Technical Parameters Model Function Rated Voltage Rated Frequency Fan Type-Piece Diameter-Length in. (mm) Evaporator Pipe Diameter in. (mm) Row-Fin Gap in. (mm) Indoor Coil Length x Height x Width in. (mm) Side Swing Motor Model Output of Swing Motor Fuse (A) Sound Pressure Level dB (A) (H/M/L) Sound Power Level dB (A) (H/M/L) Compressor Manufacturer/Trademark Compressor Model Compressor Type L.R.
Heat Controller Model Function Rated Voltage Rated Frequency Fan Type-Piece Diameter-Length in. (mm) Evaporator Pipe Diameter in. (mm) Row-Fin Gap in. (mm) Indoor Coil Length x Height x Width in. (mm) Side Swing Motor Model Output of Swing Motor Fuse (A) Sound Pressure Level dB (A) (H/M/L) Sound Power Level dB (A) (H/M/L) Compressor Manufacturer/Trademark Compressor Model Compressor Type L.R.
PACKAGED TERMINAL A/C Model Function Rated Voltage Rated Frequency Fan Type-Piece Diameter-Length in. (mm) Evaporator Pipe Diameter in. (mm) Row-Fin Gap in. (mm) Indoor Coil Length x Height x Width in. (mm) Side Swing Motor Model Output of Swing Motor Fuse (A) Sound Pressure Level dB (A) (H/M/L) Sound Power Level dB (A) (H/M/L) Compressor Manufacturer/Trademark Compressor Model Compressor Type L.R.
Heat Controller Model Function Rated Voltage Rated Frequency Fan Type-Piece Diameter-Length in. (mm) Evaporator Pipe Diameter in. (mm) Row-Fin Gap in. (mm) Indoor Coil Length x Height x Width in. (mm) Side Swing Motor Model Output of Swing Motor Fuse (A) Sound Pressure Level dB (A) (H/M/L) Sound Power Level dB (A) (H/M/L) Compressor Manufacturer/Trademark Compressor Model Compressor Type L.R.
PACKAGED TERMINAL A/C Model Function Rated Voltage Rated Frequency Fan Type-Piece Diameter-Length in. (mm) Evaporator Pipe Diameter in. (mm) Row-Fin Gap in. (mm) Indoor Coil Length x Height x Width in. (mm) Side Swing Motor Model Output of Swing Motor Fuse (A) Sound Pressure Level dB (A) (H/M/L) Sound Power Level dB (A) (H/M/L) Compressor Manufacturer/Trademark Compressor Model Compressor Type L.R.
Heat Controller Model Function Rated Voltage Rated Frequency Fan Type-Piece Diameter-Length in. (mm) Evaporator Pipe Diameter in. (mm) Row-Fin Gap in. (mm) Indoor Coil Length x Height x Width in. (mm) Side Swing Motor Model Output of Swing Motor Fuse (A) Sound Pressure Level dB (A) (H/M/L) Sound Power Level dB (A) (H/M/L) Compressor Manufacturer/Trademark Compressor Model Compressor Type L.R.
PACKAGED TERMINAL A/C Model Function Rated Voltage Rated Frequency Fan Type-Piece Diameter-Length in. (mm) Evaporator Pipe Diameter in. (mm) Row-Fin Gap in. (mm) Indoor Coil Length x Height x Width in. (mm) Side Swing Motor Model Output of Swing Motor Fuse (A) Sound Pressure Level dB (A) (H/M/L) Sound Power Level dB (A) (H/M/L) Compressor Manufacturer/Trademark Compressor Model Compressor Type L.R.
Heat Controller Model Function Rated Voltage Rated Frequency Fan Type-Piece Diameter-Length in. (mm) Evaporator Pipe Diameter in. (mm) Row-Fin Gap in. (mm) Indoor Coil Length x Height x Width in. (mm) Side Swing Motor Model Output of Swing Motor Fuse (A) Sound Pressure Level dB (A) (H/M/L) Sound Power Level dB (A) (H/M/L) Compressor Manufacturer/Trademark Compressor Model Compressor Type L.R.
PACKAGED TERMINAL A/C Heat Controller Service Manual Extended Performance Data EXTENDED COOLING PERFORMANCE OUTDOOR DRY BULB TEMP. (DEGREES F AT 40% R.H.) 75 85 95 105 110 INDOOR WET BULB TEMP. (DEGREES F AT 80 F D.B.) EKTC07 EKTC09 EKTC12 EKTC15 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 BTUh 9055 8709 8062 8624 8131 7500 8285 7700 6815 7762 6892 6076 6907 5944 5251 WATTS 522 530 536 569 575 582 640 640 640 691 691 693 755 755 758 AMPS 2.5 2.
Heat Controller Service Manual Extended Performance Data continued EXTENDED HEATING PERFORMANCE OUTDOOR DRY BULB TEMP. (DEGREES F) 37 42 47 52 57 EKTH07 EKTH09 EKTH12 EKTH15 BTUh 5250 5540 6300 6899 7620 WATTS 509 518 540 549 580 AMPS 2.4 2.5 2.5 2.6 2.7 BTUh 6004 6399 8100 8647 9244 WATTS 646 656 720 725 735 AMPS 3.5 3.5 3.6 3.6 3.7 BTUh 7726 8531 10700 11278 12235 WATTS 883 917 1010 1040 1073 AMPS 4.2 4.3 4.7 4.9 5.
PACKAGED TERMINAL A/C Service Manual Heat Controller Controller Functions and Operating Methods The relationship between Centigrade and Fahrenheit is: Tcentigrade=Tfahrenheit*1.8+3.2 A. Temperature Parameter n Indoor setting temperature (Tpeset) n Indoor ambient temperature (Tamb) B. System Basic Function The compressor has a 3 minute time delay before it will start as a protective feature. Once the compressor begins to run, the compressor cannot be stopped by changing the set temperature.
Heat Controller Service Manual Packaged Terminal A/C Controller Function and Operating Method continued 7. Open circuit and short circuit of temperature sensor If the temperature sensor has an open circuit, it will send an error signal. The error signal is displayed (see table below).
PACKAGED TERMINAL A/C Service Manual Heat Controller D. Special Functions and Features The PTAC unit is designed to be operated by the unit’s main control panel, however, factory installed connections are included to allow the PTAC to operate via remote thermostat or energy management input (front desk control).
Heat Controller Service Manual SUGGESTIONS: 1. To size transformer, use the following equation: Quantity of PTAC units x 12 va=Transformer Size (va) Example: 110 PTAC units x 12 va = 1320 vaTransformer 2. Following are American Wire Gauge recommended sizes: AWG WIRE SIZE NO.
PACKAGED TERMINAL A/C Service Manual Heat Controller Wall Thermostat Connections A standard low voltage wall thermostat can be wed with the PTAC unit’s factory installed terminal. Multiple PTACs can even be connected together on a single wall thermostat.
Heat Controller Service Manual Typical Wiring Diagram 18 Packaged Terminal A/C
PACKAGED TERMINAL A/C Service Manual Heat Controller E. Unit controls The PTAC can be configured by the display and a set of dip switches. 1. TEMP CONTROL Temp Control is used to maintain room temperature. Compressor will cycle on and off to keep room at the requested level of comfort. COOLER—Lowers temperature. (Minimum temperature setting is 61°F/16°C) WARMER—Raises temperature. (Maximum temperature setting is 86°F/30°C) 2. FAN SPEED, MODE & ON/OFF FAN SPEED—Set fan operation for HI, MED, or LO speed.
Heat Controller Service Manual Packaged Terminal A/C KEYPAD CONFIGURATION Allows further configuration of system to desired application such as whether th unit displays in °F or °C, whether the display shows the set point or room air temperature, and to set controls for sensor biasing. Changes do not take affect until power is cycled on the unit. To enter Keypad configuration Cycle power to unit.
PACKAGED TERMINAL A/C Heat Controller Service Manual DIP SWITCHES Auxiliary dip switch controls are located behind front panel, through an opening below the control panel. Dip switches are accessible without opening the control box. Unit must be powered OFF to effectively change their status. Factory settings for dip switches will be in the DOWN position. See Table—Dip Switch Functions for functions of each dip switch position.
Heat Controller Service Manual Packaged Terminal A/C F. Protective Features 1. Frost Protection Mode (heat pump): When the compressor is running under wired controller’s heating signal. If T outer tube ≤ 28°F (-2°C) is detected for 1 minute successively, the compressor and outdoor fan will stop running. Then indoor fan will run normally according to the wired controller’s signal. If the heating is required then the heat pump operation will stop the compressor and run the electric heater solely.
5 Electric Circuit Diagram PACKAGED TERMINAL A/C Service Manual Electric Circuit Diagram This electrical diagram is subject to change. Please refer to the diagram in the actual unit.
Heat Controller Service Manual Packaged Terminal A/C POWER CONNECTION OPTIONS Appropriate power cord accessory kit is determined by the voltage, and amperage of the branch circuit. The unit does not come with a power cord (or hard wire kit). An accessory power cord kit must be ordered to connect the unit to the outlet. If the unit is to be hard wired, an accessory hard wire kit must be ordered. IMPORTANT: For 265V units, if a power cord is selected, it must plug into the 265V subbase accessory.
PACKAGED TERMINAL A/C Service Manual Heat Controller PREVENTATIVE MAINTENANCE Preventative maintenance is essential to proper unit operation, efficiency and longevity. To ensure equipment operates properly, it must be properlymaintained. Equipment operation should be checked and verified several times during each year. During regular unit inspection and maintenance, follow the guidelines below: • Clean both sides of outdoor coil. (Never use high pressure spray on coils.
Rated Frequency Total Capacity (Btu/h) HeatInput Controller Service Manual Power (W) Rated Input (W) Rated Current (A) 3 Trouble Guide Air Flow Volume CFM (mShooting /h) Model Dehumidifying Volume pint/hour (l/h) Product code EER / C.O.P (W/W) Function Energy Class Rated Voltage Fan Type-Piece Rated Frequency Diameter-Length in. (mm) Total Capacity (Btu/h) Evaporator Power Input (W) Pipe Diameter in. (mm) Rated Input (W) Row-Fin IndoorCurrent (A) Gap in. (mm) Rated Coil length X height X coil width in.