NOMINAL 5 TONS
Model
TGC060C-1K-135 TGC060C-3K-135 TGC060C-4K-135
Cooling Performance
1
Gross Cooling Capacity Btuh 60000 60000 60000
EER/SEER
2
11.6/13 11.6/13 11.6/13
Nominal CFM/ARI Rated CFM 2000/1900 2000/1900 2000/1900
ARI Net Cooling Capacity Btuh 58000 58000 58000
Net Sensible Capacity Btuh 42000 42000 42000
Net Latent Capacity Btuh 16000 16000 16000
Net System Power kW 5 5 5
Heating Performance (Package Gas/Electric)
3
Heating Input Btuh 135000 135000 135000
Heating Output Btuh 106500 109400 109400
Temperature Rise ºF 40-70 40-70 40-70
AFUE (%) 80 80 80
Steady State Efficiency (%) 81 81 81
Qty of Burners 6 6 6
Qty of Stages 1 1 1
Gas Connection Pipe Size, in. .5 .5 .5
Compressor
Qty/Type
Outdoor Sound Rating (dB) 83 78 78
Outdoor Coil—Fin Type
Tube Type Rifled Rifled Rifled
Tube Size in. OD 0.375 0.375 0.375
Face Area sq. ft. 16.56 16.56 16.56
Rows / Fins per inch 2/22 2/22 2/22
Indoor Coil—Fin Type
Tube Type Rifled Rifled Rifled
Tube Size in. 0.375 0.375 0.375
Face Area sq. ft. 5.17 5.17 5.17
Rows / Fins per inch 3/15 3/15 3/15
Refrigerant Control TXV TXV TXV
Drain Connection Qty/Size, in. 1/0.75 1/0.75 1/0.75
Outdoor Fan—Type
Qty Used/Diameter in. 1/24 1/24 1/24
Drive Type/Speeds Direct/1 Direct/1 Direct/1
CFM 3930 3930 3930
Qty Motors-HP 1-1/3 1-1/3 1-1/3
Motor RPM 1075 1075 1075
Indoor Fan—Type
Qty Used/Diameter in. 1/10x10 1/10x10 1/10x10
Drive Type/Speeds Direct/3 Direct/3 Belt/Variable
Motor Qty 1 1 1
Motor HP 1 1 3/4
Motor RPM 1075 1075 1725
Motor Frame Size 48 48 56
Filter—Type
Furnished Yes Yes Yes
(Qty) Size Recommended in. (2)16x25x1 (2)16x25x1 (2)16x25x1
Refrigerant Charge Oz. 160 160 160
Weights
Net Weight lbs. 597 597 597
Ship Weight lbs. 604 604 604
Notes:
Forward Curved Centrifugal
Disposable
1/Copeland Scroll
Louvered
Corrugated
Propeller
1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan
motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units
are certified and rated per ARI Standard 210/240.
2. EER/SEER are rated ARI condition and accordance with DOE test procedures.
3. Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National
Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each
1000 feet above sea level.