End View of a Saf-T Vent GC or CI Section or Fitting
5. Connecting Saf-T Vent GC or Saf-T Vent CI to EZ Seal
• Saf-T Vent GC and Saf-T Vent CI sections and fittings may be attached to an EZ Seal
system:
• If the male end (without tabs) of the GC or CI part was made with a butt-weld (a single layer
of steel at the weld area), the part can be attached to an EZ Seal female end without using
sealant.
• If the male end was made with an overlapped weld (two layers of steel at the weld area),
the joint must be made using an approved high-temperature RTV silicone sealant. Follow
the procedure outlined in the GC or CI installation instructions (Pub # PI-VBH or PI-CIINS).
Use of Sealant Depends on the Type of Weld
EZ SEAL
SAF-T VENT GC
EZ SEAL
SAF-T VENT CI
No Sealant required
Butt Weld
Single Layer of Steel
Overlap Weld
Two Layers of Steel
Sealant required