Installation Guide

www.heat-fab.com eng@heat-fab.com
413.863.2242 800.772.0739 fax 413.863.4803
Pub # 11719-091401 130 Industrial Boulevard Turners Falls MA 01376
End View of a Saf-T Vent GC or CI Section or Fitting
5. Connecting Saf-T Vent GC or Saf-T Vent CI to EZ Seal
Saf-T Vent GC and Saf-T Vent CI sections and fittings may be attached to an EZ Seal
system:
If the male end (without tabs) of the GC or CI part was made with a butt-weld (a single layer
of steel at the weld area), the part can be attached to an EZ Seal female end without using
sealant.
If the male end was made with an overlapped weld (two layers of steel at the weld area),
the joint must be made using an approved high-temperature RTV silicone sealant. Follow
the procedure outlined in the GC or CI installation instructions (Pub # PI-VBH or PI-CIINS).
Use of Sealant Depends on the Type of Weld
EZ SEAL
SAF-T VENT GC
EZ SEAL
SAF-T VENT CI
No Sealant required
Butt Weld
Single Layer of Steel
Overlap Weld
Two Layers of Steel
Sealant required