Specification Sheet

Heatfab, Div. Selkirk Corp. Product Specifications subject to change
without Notice. All Rights Reserved. Saf-T Vent is a registered
trademark of Selkirk Corp.. AL 29-4C is a registered trademark
of ATI Properties, Inc..
www.heatfab.com 130 Industrial Blvd., Turners Falls, MA 01376
Pub #11439-102207
TECHNICAL SPECIFICATION
Product Saf-T Vent EZ Seal Special Gas Vent
Saf-T Vent EZ Seal Gas Vent Connector
Uses Vents (Horizontal or Vertical) for Gas
Burning Appliances, suitable for ANSI
Category I, II, III, and IV Gas-Burning
Appliances.
Fuels Natural gas or propane fired equipment
Pressure Positive up to 8” wc, negative, or neutral
Standard
Diameters 3”-16”
Lengths 6”, 12”, 18”, 24”, 36”, adjustable length,
and 60” in 3” & 4” diameters only.
Flue-Gas
Conduit AL 29-4C
®
stainless steel
The Saf-T Vent
®
EZ Seal systems are to be installed
only in accordance with Heatfab, “Installation and
Maintenance Instructions” and with all applicable local,
regional, and national codes.
The Saf-T Vent EZ Seal factory-built Special Gas Vent
and Gas Vent Connector is Tested and Listed by
Underwriters Laboratories to UL 1738 /ULC S636 for
use with Listed natural gas or propane burning
equipment that produce flue-gas temperatures not
above 550°F. Some applications have lower maximum
temperatures. The system is to be installed and sealed
per the manufacturers’ instructions so all joints are
gas tight, preventing leakage of products of combustion
into a building.
The Saf-T Vent EZ Seal system is fabricated from
AL 29-4C
®
stainless steel, which is highly suited for
use with high efficiency gas burning equipment, which
produce excessive amounts of condensation in the vent.
All joints in the Saf-T Vent EZ Seal system are fastened
with the patented Ring and Tab tapered closure system
and sealed with factory applied seal. This closure
system is tested to be gas tight at two and one-half
times the Listed pressure rating of 8" water column.
When properly installed using the Heatfab supplied
materials, the system may safely and securely be
utilized in all interior installations and may pass through
combustible exterior roofs or walls using the appropriate
thimble devices available from Heatfab. The system
may pass through interior partitions and floors provided
proper clearances are adhered to. If the venting system
must extend exposed to the outdoors for more than
3 feet, we recommend using the Saf-T Vent CI Plus
double-wall Special Gas Vent system.
When connected to gas-burning appliances with a
maximum continuous flue-gas temperature rating of
550°F, Saf-T Vent EZ Seal may be installed adjacent
to combustible materials on a maximum of 3 sides
only at 2” clearance.
When connected to gas-burning appliances with a
maximum continuous flue-gas temperature rating of
300°F, Saf-T Vent EZ Seal may be installed adjacent
to combustible materials on a maximum of 3 sides
only at 1” clearance.
When connected to gas-burning appliances with a
maximum continuous flue-gas temperature rating of
480°F, Saf-T Vent EZ Seal may be enclosed by com-
bustibles with an air space clearance of 8” horizontally
or 6” vertically.
The Saf-T Vent EZ Seal system is to be sized in
accordance with appliance manufacturers’
specifications, the most current edition of NFPA 211
Standard for Chimneys, Fireplaces, Vents, and Solid
Fuel-Burning Appliances, the most current edition of
NFPA 54 National Fuel Gas Code (ANSI Z223.1), and
all applicable local and regional codes.
Saf-T Vent
®
EZ Seal Specifications for Special Gas Vent Applications

Summary of content (34 pages)