Specification Sheet

Saf-T Vent
®
EZ Seal
130 Industrial Boulevard • Turners Falls, MA 01376
Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.com
SINGLE WALL AL 29-4C
®
SPECIAL GAS VENT
14
Heatfab
18" Length Install vent with a continuous pitch of 1/4” per foot, sloping upward toward the termination (unless
otherwise specified by the appliance manufacturer). It is important to provide adequate support to a Saf-T Vent EZ Seal
system. Support horizontal portions of the vent system at 6-foot intervals. Vertical sections should be supported at least every
30-feet and after every offset or transition.
Straight Lengths:
Part Number DIM - A DIM - B DIM - C
Nominal Diameter Installed Length Maximum OD
9304 3 16.5 3.4
9404 4 16.5 4.4
9504 5 16.5 5.4
9604 6 16.5 6.4
9704 7 16.5 7.4
9804 8 16.5 8.4
9904 9 16.5 9.4
91004 10 16.5 10.4
91204 12 16.5 12.4
91404 14 16.5 14.4
91604 16 16.5 16.4
Adjustable Length Use to accommodate distances not possible with the standard Saf-T Vent EZ Seal lengths.
The slip connector serves as an adjustable section and eliminates the need to cut parts to length. The Slip Connector can have
an installed length from 6 to 19 inches. It works best in conjunction with another straight length of Saf-T Vent EZ Seal. When
used with an elbow or a tee, do not insert the Slip Connector so far that air flow within the vent becomes obstructed. When
planning a venting system, include one slip connector for every change of direction and for any spans between two fixed
points. Each slip connector comes with three components, a slip section, a male connector and a stainless steel hose clamp.
Part Number DIM - A DIM - B DIM - C DIM - D
Nominal Minimum Maximum Slip
Diameter Installed Length Installed Length Diameter
9324 3.1 6 19 3.00
9424 4 6 19 3.90
9524 5 6 19 4.90
9624 6 6 19 5.87
9724 7 6 19 6.85
9824 8 6 19 7.89
9924 9 6 19 8.86
91024 10 6 19 9.86
91224 12 6 19 11.86
91424 14 6 19 13.87
91624 16 6 19 15.86
C
A
B
B
A
C
D