Specification Sheet

Saf-T Vent
®
EZ Seal
130 Industrial Boulevard • Turners Falls, MA 01376
Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.com
SINGLE WALL AL 29-4C
®
SPECIAL GAS VENT
15
Heatfab
2 Ft. Length Install vent with a continuous pitch of 1/4” per foot, sloping upward toward the termination (unless
otherwise specified by the appliance manufacturer). It is important to provide adequate support to a Saf-T Vent EZ Seal system.
Support horizontal portions of the vent system at 6-foot intervals. Vertical sections should be supported at least every 30-feet
and after every offset or transition.
Straight Lengths:
Part Number DIM - A DIM - B DIM - C
Nominal Diameter Installed Length Maximum OD
9305 3 22.5 3.4
9405 4 22.5 4.4
9505 5 22.5 5.4
9605 6 22.5 6.4
9705 7 22.5 7.4
9805 8 22.5 8.4
9905 9 22.5 9.4
91005 10 22.5 10.4
91205 12 22.5 12.4
91405 14 22.5 14.4
91605 16 22.5 16.4
3 Ft. Length Install vent with a continuous pitch of 1/4” per foot, sloping upward toward the termination (unless
otherwise specified by the appliance manufacturer). It is important to provide adequate support to a Saf-T Vent EZ Seal system.
Support horizontal portions of the vent system at 6-foot intervals. Vertical sections should be supported at least every 30-feet
and after every offset or transition.
Part Number DIM - A DIM - B DIM - C
Nominal Diameter Installed Length Maximum OD
9307 3 36 3.4
9407 4 36 4.4
9507 5 36 5.4
9607 6 36 6.4
9707 7 36 7.4
9807 8 36 8.4
9907 9 34.5 9.4
91007 10 34.5 10.4
91207 12 34.5 12.4
91407 14 34.5 14.4
91607 16 34.5 16.4