Normal operation of gas burning appliances does not result in deposits of combustible soot in venting
systems. However, a poorly adjusted or malfunctioning appliance can deposit soot and other debris
which can enter the vent system. As with all vents, the Saf-T Vent CI Plus system should be inspected
at least annually for the presence of deposits of soot or debris. Any such accumulation should be
removed and the appliances adjusted to eliminate future accumulation.
At regular periods the system should also be inspected for signs of leakage of condensate or
combustion by-products at all joints. If any leakage is found the connected appliances should be turned
off and the leaks repaired.
If the system incorporates a drain hose from either an in-line fitting or from a drain tee then the hose
must be inspected periodically to assure that water remains in the trap loop. If a proper trap loop is not
maintained exhaust from the connected appliances may accumulate in the building area.
Maintenance Procedures: