Specification Sheet

Flue Temperature
At Appliance Oulet
Typical Outside Skin Temperature
Saf-T Vent CI and Saf-T Vent CI Plus
6” Diameter at 4 Hour Continuous Operation
www.heat-fab.com 800.772.0739
Outside Skin Temperature
at 72” Vertical
Outside Skin Temperature
at 96” Vertical
Outside Skin Temperature
at 60” Vertical
Outside Skin Temperature
at 24” Vertical
Outside Skin Temperature
From 96” Vertical
To 60” Horizontal
Outside Skin Temperature
From 96” Vertical
To 120” Horizontal
Flow
Pub # 11732 021105
Location Location Location Location Location Location
Saf-T Vent CI 300°F / 149°C 75°F / 24°C 170°F / 77°C 137°F / 58°C 143°F / 62°C 148°F / 64°C 146°F / 63°C 134°F / 57°C
Saf-T Vent CI 380°F / 193°C 75°F / 24°C 212°F / 100°C 168°F / 76°C 171°F / 77°C 177°F / 81°C 173°F / 78°C 162°F / 72°C
Saf-T Vent CI 420°F / 216°C 75°F / 24°C 225°F / 107°C 176°F / 80°C 176°F / 80°C 190°F / 88°C 179°F / 82°C 169°F / 76°C
Saf-T Vent CI Plus 300°F / 149°C 75°F / 24°C 100°F / 38°C 110°F / 43°C 120°F / 49°C 135°F / 57°C 142°F / 61°C 132°F / 56°C
Saf-T Vent CI Plus 380°F / 193°C 75°F / 24°C 132°F / 56°C 124°F / 51°C 129°F / 58°C 149°F / 65°C 164°F / 73°C 151°F / 66°C
Saf-T Vent CI Plus 420°F / 216°C 75°F / 24°C 138°F / 59°C 138°F / 59°C 126°F / 52°C 157°F / 69°C 170°F / 77°C 161°F / 72°C
96" Vertical &
120" Horizontal
60" Vertical 72" Vertical 96" Vertical
96" Vertical &
60" Horizontal
Model Double Wall
6" Diameter
A
ppliance Outlet
Flue Temperature
Room Ambient
Temperature
24" Vertical
C
A
B
D E F