Installation Guide

11
Condensate Drains:
When An Internal Condensate Drain Is NOT Part of the Appliance:
A Saf-T Vent SC In-Line Drain Section is strongly recommended. Install this drain fitting as close to
the appliance flue collar as possible.
A condensate drain is required for every 30 feet of horizontal vent and at/near the bottom of a
vertical stack.
Use the In-Line Drain Section for a straight horizontal or vertical run. When used horizontally, rotate the
fitting so that the drain tube is as vertical as possible.
A Condensate Drain Tube Kit is available to direct the condensate to an appropriate location, i.e. floor
drain or vented sanitary sewer connection. A trap loop must be formed into the drain hose and must be a
diameter that is at least four times the appliance's rated stack pressure in inches of water column or 3
inches, whichever is greater. Secure the loop with a cable tie. Prior to final assembly the trap loop must
be 'primed' by pouring a small quantity of water into the drain hose. Inspect at least annually to verify the
trap is 'primed'.
Follow all local and national codes and regulations for the draining of acidic condensate.
In cold climates do not install a condensate drain on the exterior of the building. Doing so may result in
dangerous icy conditions on surfaces near the drain and may cause damage to the vent system and/ or
the building exterior. Heat-fab, Inc. will NOT be held liable for any injury or property damage due to
formation of ice.
Horizontal Installation
As An Exhaust System Only
Typical SC Connections and Drain Placements:
Saf -T Vent SC Air Intake System
Must Be Approved by the
Appliance Manufacturer
Saf -T Vent SC As An
Exhaust System Only